Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 6, 2021, 09:45 AM
  • 05 1864_05 1863_08062021_025521.mp4

Date
08/06/2021
W/O
906772
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00490
PipeID
P07089
Time
2:45 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9098
Sewer Name
05 NARBONNE AVENUE TRUNK, SECTION 1(EAST)
City
LOMITA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
35
Purpose
Routine Assessment
Project
WO_906772_TV05076_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
27 in.
Upstream MH
05 1864
Downstream MH
05 1863
Dir. of Survey
Downstream
Length Surveyed
273.6 ft.
Total Length
273.6 ft.
Structural Index
2
Structural Quick
2J00
Structural Rating
108
O&M Index
2
O&M Quick
2J00
O&M Rating
108
Overall Index
2
Overall Quick
Overall Rating
216
Pipe schematic from manhole 05 1864 to 05 1863
MH: 05 1864MH: 05 1863downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 18640 ft. MWM - Water Mark, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start14.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN41.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN90.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"140.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - 10% ROOTS/GREASE-LATERAL181.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"215.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"263.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"271 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish271 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish273.6 ft. AMH - Downstream Manhole, Survey Ends - 05 1863

Observation photos (1)

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

    41.2 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

Observations (15)

DistanceCodeObservation
271SSS
271DAGS
273.6AMH05 1863
0MWL
140.8TFA10% ROOTS/GREASE-LATERAL
0AMH05 1864
263.1TFA
41.2TBOPEN
2DAGS
215.7TFA
181.5TFC
90.5TFA
14.5TFOPEN
0MWM
2SSS

Properties (7)

additional_info
630074080521201
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2021-08-06T02:45:03-07:00
documentation
PROPIPE
is_lateral_inspection