Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 6, 2021, 10:25 AM
  • 05 1861_05 1860_08062021_035041.mp4

Date
08/06/2021
W/O
906772
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00490
PipeID
P07086
Time
3:25 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9098
Sewer Name
05 NARBONNE AVENUE TRUNK, SECTION 1(EAST)
City
LOMITA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
35
Purpose
Routine Assessment
Project
WO_906772_TV05076_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
15 in.
Upstream MH
05 1860
Downstream MH
05 1861
Dir. of Survey
Upstream
Length Surveyed
339.9 ft.
Total Length
339.9 ft.
Structural Index
2
Structural Quick
5131
Structural Rating
146
O&M Index
2
O&M Quick
2M00
O&M Rating
138
Overall Index
2
Overall Quick
Overall Rating
284
Pipe schematic from manhole 05 1860 to 05 1861
MH: 05 1860MH: 05 1861upstream0 ft. AMH - Upstream Manhole, Survey Ends - 05 18612.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish10.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"24.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES45.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN115.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN134.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES138.6 ft. HSV - Hole Soil Visible, at 09 o'clock, within 8 inches of joint: YES140.2 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"185.2 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OFFSET CONN/OPEN206.4 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"220.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"245.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES246.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN264.2 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"283.3 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"318.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"337.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start337.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start339.9 ft. MWL - Water Level, 10 %of cross sectional area339.9 ft. AMH - Downstream Manhole, Survey Begins - 05 1860339.9 ft. MWM - Water Mark, 15 %of cross sectional area

Observation photos (7)

  • Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"

    56.6 ft. - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"

  • Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    75.7 ft. - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    94 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"

    199.7 ft. - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"

  • Hole Soil Visible, at 09 o'clock, within 8 inches of joint: YES

    201.3 ft. - Hole Soil Visible, at 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    205.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    315.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (23)

DistanceCodeObservation
315.8CL
93.7TFOPEN
0MWL
339.9AMH05 1861
56.6TBA
133.5TBA
201.3HSV
119.6TFC
2SSS
329.2TFA
154.7TFDOFFSET CONN/OPEN
337SSS
337DAGS
2DAGS
294TFOPEN
94CM
205.7CL
0AMH05 1860
224TFOPEN
199.7TBA
75.7TBC
21.2TFA
0MWM

Properties (7)

additional_info
630074080521201
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2021-08-06T03:25:02-07:00
documentation
PROPIPE
is_lateral_inspection
false