Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 6, 2021, 08:31 AM
  • 05 1859_05 1858_08062021_013724.mp4

Date
08/06/2021
W/O
906772
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00490
PipeID
P07084
Time
1:31 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9098
Sewer Name
05 NARBONNE AVENUE TRUNK, SECTION 1(EAST)
City
LOMITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
35
Purpose
Routine Assessment
Project
WO_906772_TV05076_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
15 in.
Upstream MH
05 1858
Downstream MH
05 1859
Dir. of Survey
Upstream
Length Surveyed
155.3 ft.
Total Length
155.3 ft.
Structural Index
2
Structural Quick
2E00
Structural Rating
60
O&M Index
2
O&M Quick
2E00
O&M Rating
60
Overall Index
2
Overall Quick
Overall Rating
120
Pipe schematic from manhole 05 1858 to 05 1859
MH: 05 1858MH: 05 1859upstream0 ft. AMH - Upstream Manhole, Survey Ends - 05 18592.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish153.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start153.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start155.3 ft. MWM - Water Mark, 20 %of cross sectional area155.3 ft. AMH - Downstream Manhole, Survey Begins - 05 1858155.3 ft. MGO - General Observation - ROACHES @ MH155.3 ft. MWL - Water Level, 15 %of cross sectional area

Observations (9)

DistanceCodeObservation
0MWM
2DAGS
0AMH05 1858
155.3AMH05 1859
0MGOROACHES @ MH
0MWL
153SSS
153DAGS
2SSS

Properties (7)

additional_info
630074080521201
custom_field_three
NO SEVERE DEFECTS
custom_field_two
4
customer
1
datetime
2021-08-06T01:31:52-07:00
documentation
PROPIPE
is_lateral_inspection
false