Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 6, 2021, 05:53 AM
  • 05 1853_05 1852_08052021_230518.mp4

Date
08/05/2021
W/O
906772
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00490
PipeID
P07078
Time
10:53 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9098
Sewer Name
05 NARBONNE AVENUE TRUNK, SECTION 1(EAST)
City
LOMITA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
35
Purpose
Routine Assessment
Project
WO_906772_TV05076_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
15 in.
Upstream MH
05 1853
Downstream MH
05 1852
Dir. of Survey
Downstream
Length Surveyed
355.8 ft.
Total Length
355.8 ft.
Structural Index
2
Structural Quick
2M00
Structural Rating
140
O&M Index
2
O&M Quick
2M00
O&M Rating
140
Overall Index
2
Overall Quick
Overall Rating
280
Pipe schematic from manhole 05 1853 to 05 1852
MH: 05 1853MH: 05 1852downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 18532 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start89.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN144 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"195.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"228.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - 10% GREASE-LATERAL/OPEN291.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"333.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN353 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish353 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish355.8 ft. AMH - Downstream Manhole, Survey Ends - 05 1852

Observations (14)

DistanceCodeObservation
2DAGS
291.6TFC
0MWL
353DAGS
0MWM
195.6TFA
0AMH05 1853
144TFC
228.2TF10% GREASE-LATERAL/OPEN
2SSS
353SSS
333.5TFOPEN
355.8AMH05 1852
89.9TFOPEN

Properties (7)

additional_info
630074080521201
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2021-08-05T22:53:16-07:00
documentation
PROPIPE
is_lateral_inspection
false