Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 6, 2021, 06:05 AM
  • 05 1852_05 1851_08052021_231945.mp4

Date
08/05/2021
W/O
906772
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00490
PipeID
P07077
Time
11:05 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9098
Sewer Name
05 NARBONNE AVENUE TRUNK, SECTION 1(EAST)
City
LOMITA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
35
Purpose
Routine Assessment
Project
WO_906772_TV05076_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
15 in.
Upstream MH
05 1852
Downstream MH
05 1851
Dir. of Survey
Downstream
Length Surveyed
354 ft.
Total Length
354 ft.
Structural Index
2
Structural Quick
2M00
Structural Rating
140
O&M Index
2
O&M Quick
2M12
O&M Rating
142
Overall Index
2
Overall Quick
Overall Rating
282
Pipe schematic from manhole 05 1852 to 05 1851
MH: 05 1852MH: 05 1851downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 18520 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start23.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"58.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"95.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"122.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"210.4 ft. RFL - Roots Fine Lateral, at 02 o'clock - 10% ROOTS-LATERAL210.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN230.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN285.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"309.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN328.4 ft. RFJ - Roots Fine Joint, from 07 to 09 o'clock, within 8 inches of joint: YES333.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN351 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish351 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish354 ft. AMH - Downstream Manhole, Survey Ends - 05 1851

Observation photos (1)

  • Roots Fine Joint, from 07 to 09 o'clock, within 8 inches of joint: YES

    328.4 ft. - Roots Fine Joint, from 07 to 09 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
95.6TFC
210.4RFL10% ROOTS-LATERAL
23.7TFA
2DAGS
351DAGS
0MWM
328.4RFJ
58.9TFA
122.4TFA
0AMH05 1852
309.3TFOPEN
333.2TFOPEN
210.4TFOPEN
2SSS
354AMH05 1851
230.9TFOPEN
0MWL
351SSS
285.4TFC

Properties (7)

additional_info
630074080521201
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2021-08-05T23:05:29-07:00
documentation
PROPIPE
is_lateral_inspection
false