Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 6, 2021, 04:18 AM
  • 05 1850_05 1837_08052021_220955.mp4

Date
08/05/2021
W/O
906772
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00490
PipeID
P07075
Time
9:18 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9098
Sewer Name
05 NARBONNE AVENUE TRUNK, SECTION 1(EAST)
City
LOMITA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
35
Purpose
Routine Assessment
Project
WO_906772_TV05076_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
15 in.
Upstream MH
05 1850
Downstream MH
05 1837
Dir. of Survey
Downstream
Length Surveyed
355.3 ft.
Total Length
355.3 ft.
Structural Index
2
Structural Quick
2M00
Structural Rating
140
O&M Index
2
O&M Quick
412M
O&M Rating
144
Overall Index
2
Overall Quick
Overall Rating
284
Pipe schematic from manhole 05 1850 to 05 1837
MH: 05 1850MH: 05 1837downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 18500 ft. MWL - Water Level, 30 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start22.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN46.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN133.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN145.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN211.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN222.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"280.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"353 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish353 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish355 ft. MGO - General Observation - ROACHES @ MH355.3 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE355.3 ft. AMH - Downstream Manhole, Survey Ends - 05 1837

Observations (17)

DistanceCodeObservation
145.1TFOPEN
355.3MGOCONN @ MH 9 O'CLOCK/ACTIVE
0MWM
0AMH05 1850
355MGOROACHES @ MH
133.5TFOPEN
222.3TFA
280.2TFC
211.7TFOPEN
353DAGS
2DAGS
355.3AMH05 1837
353SSS
2SSS
22.3TFOPEN
0MWL
46.7TFOPEN

Properties (7)

additional_info
630074080521201
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2021-08-05T21:18:31-07:00
documentation
PROPIPE
is_lateral_inspection
false