Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 6, 2021, 06:51 AM
  • 02 1169_02 1166_08062021_000850.mp4

Date
08/05/2021
W/O
906537
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00350
PipeID
P04563
Time
11:51 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9223
Sewer Name
02 GARFIELD AVENUE TRUNK
City
MONTEBELLO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
WO_906537_TV02062_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
24 in.
Upstream MH
02 1169
Downstream MH
02 1166
Dir. of Survey
Downstream
Length Surveyed
327.2 ft.
Total Length
327.2 ft.
Structural Index
4
Structural Quick
4L34
Structural Rating
264
O&M Index
2
O&M Quick
412L
O&M Rating
134
Overall Index
3
Overall Quick
Overall Rating
398
Pipe schematic from manhole 02 1169 to 02 1166
MH: 02 1169MH: 02 1166downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 02 11690 ft. MWL - Water Level, 5 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start10.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11.7 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"24.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"75.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"127 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"165.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"177.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"203.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"226.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"265.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"301.2 ft. MWLS - Water Level, Sag in pipe, 50 %of cross sectional area, Start323.3 ft. MWLS - Water Level, Sag in pipe, 50 %of cross sectional area, Finish325.6 ft. MGO - General Observation - COCKROACHES IN MANHOLE325.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish325.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish327.2 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK327.2 ft. AMH - Downstream Manhole, Survey Ends - 02 1166

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Water Level, Sag in pipe, 50 %of cross sectional area, Start

    301.2 ft. - Water Level, Sag in pipe, 50 %of cross sectional area, Start

  • General Observation - COCKROACHES IN MANHOLE

    325.6 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (22)

DistanceCodeObservation
11.7TB
327.2MGOCONNECTION AT MH 3 O'CLOCK
177.9TFC
265.5TFC
323.3MWLS
0MWM
0MGOCOCKROACHES IN MANHOLE
301.2MWLS
0AMH02 1169
75.4TFC
24.3TFC
127TFC
10.4FM
165.5TFA
2DAGS
325.6MGOCOCKROACHES IN MANHOLE
327.2AMH02 1166
226.2TFC
325.6FM
203.6TFA
0MWL
325.6DAGS

Properties (7)

additional_info
630069080521202
custom_field_three
FRACTURES
custom_field_two
2
customer
1
datetime
2021-08-05T23:51:23-07:00
documentation
PRO PIPE
is_lateral_inspection
false