Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 11, 2021, 10:20 AM
  • 22 0570A_22 0570_08112021_033707.mp4

Date
08/11/2021
W/O
906771
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00796
PipeID
P16916
Time
3:20 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9114
Sewer Name
22 CIENEGA AVENUE TRUNK
City
COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
20
Purpose
Routine Assessment
Project
WO_906771_TV22027_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
22 0570A
Downstream MH
22 0570
Dir. of Survey
Downstream
Length Surveyed
102 ft.
Total Length
102 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
5138
O&M Rating
33
Overall Index
3
Overall Quick
Overall Rating
33
Pipe schematic from manhole 22 0570A to 22 0570
MH: 22 0570AMH: 22 0570downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 0570A2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start24.2 ft. RMJ - Roots Medium Joint, from 08 to 04 o'clock, 25 %, within 8 inches of joint: YESR24.6 ft. RMC - Roots Medium Connection, at 11 o'clock, 20 %, within 8 inches of joint: YES24.6 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"32 ft. RMJ - Roots Medium Joint, from 08 to 04 o'clock, 20 %, within 8 inches of joint: YESR46.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"47.5 ft. RFJ - Roots Fine Joint, from 02 to 04 o'clock, within 8 inches of joint: YES55.1 ft. RMJ - Roots Medium Joint, from 08 to 04 o'clock, 20 %, within 8 inches of joint: YESR64 ft. RMJ - Roots Medium Joint, from 08 to 04 o'clock, 15 %, within 8 inches of joint: YESR68.1 ft. RMJ - Roots Medium Joint, from 08 to 04 o'clock, 5 %, within 8 inches of joint: YESR75.6 ft. RMJ - Roots Medium Joint, from 08 to 04 o'clock, 40 %, within 8 inches of joint: YESR92.4 ft. RFJ - Roots Fine Joint, from 11 to 02 o'clock, within 8 inches of joint: YES93.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"99.1 ft. RMJ - Roots Medium Joint, from 09 to 03 o'clock, 10 %, within 8 inches of joint: YESR102 ft. MSA - Survey Abandoned - DUE TO ROOTS102 ft. RBB - Roots Ball Barrell, from 08 to 03 o'clock, 60 %102 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (14)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Roots Medium Joint, from 08 to 04 o'clock, 25 %, within 8 inches of joint: YESR

    24.2 ft. - Roots Medium Joint, from 08 to 04 o'clock, 25 %, within 8 inches of joint: YESR

  • Roots Medium Connection, at 11 o'clock, 20 %, within 8 inches of joint: YES

    24.6 ft. - Roots Medium Connection, at 11 o'clock, 20 %, within 8 inches of joint: YES

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    24.6 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Roots Medium Joint, from 08 to 04 o'clock, 20 %, within 8 inches of joint: YESR

    32 ft. - Roots Medium Joint, from 08 to 04 o'clock, 20 %, within 8 inches of joint: YESR

  • Roots Fine Joint, from 02 to 04 o'clock, within 8 inches of joint: YES

    47.5 ft. - Roots Fine Joint, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Roots Medium Joint, from 08 to 04 o'clock, 20 %, within 8 inches of joint: YESR

    55.1 ft. - Roots Medium Joint, from 08 to 04 o'clock, 20 %, within 8 inches of joint: YESR

  • Roots Medium Joint, from 08 to 04 o'clock, 15 %, within 8 inches of joint: YESR

    64 ft. - Roots Medium Joint, from 08 to 04 o'clock, 15 %, within 8 inches of joint: YESR

  • Roots Medium Joint, from 08 to 04 o'clock, 5 %, within 8 inches of joint: YESR

    68.1 ft. - Roots Medium Joint, from 08 to 04 o'clock, 5 %, within 8 inches of joint: YESR

  • Roots Medium Joint, from 08 to 04 o'clock, 40 %, within 8 inches of joint: YESR

    75.6 ft. - Roots Medium Joint, from 08 to 04 o'clock, 40 %, within 8 inches of joint: YESR

  • Roots Fine Joint, from 11 to 02 o'clock, within 8 inches of joint: YES

    92.4 ft. - Roots Fine Joint, from 11 to 02 o'clock, within 8 inches of joint: YES

  • Roots Medium Joint, from 09 to 03 o'clock, 10 %, within 8 inches of joint: YESR

    99.1 ft. - Roots Medium Joint, from 09 to 03 o'clock, 10 %, within 8 inches of joint: YESR

  • Survey Abandoned - DUE TO ROOTS

    102 ft. - Survey Abandoned - DUE TO ROOTS

  • Roots Ball Barrell, from 08 to 03 o'clock, 60 %

    102 ft. - Roots Ball Barrell, from 08 to 03 o'clock, 60 %

Observations (21)

DistanceCodeObservation
102MSADUE TO ROOTS
24.6RMC
32RMJ
24.2RMJ
64RMJ
102RBB
0MWM
75.6RMJ
24.6TB
99.1RMJ
0MGOCONNECTION AT MH 3 O'CLOCK
92.4RFJ
2.1DAGS
68.1RMJ
0MWL
55.1RMJ
47.5RFJ
0AMH22 0570A
46.2TFC
102DAGS
93.5TFC

Properties (7)

additional_info
630138081021203
custom_field_three
SEVERE ROOTS, FAST FLOW CAMERA UNDERWATER
custom_field_two
5
customer
1
datetime
2021-08-11T03:20:26-07:00
documentation
PRO PIPE
is_lateral_inspection
false