Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 9, 2021, 11:15 AM
  • C 0682_C 0112_08092021_041922.mp4

Date
08/09/2021
W/O
906740
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00126
PipeID
P24965
Time
4:15 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9304
Sewer Name
C JOINT OUTFALL C - UNIT 4A
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
24
Purpose
Routine Assessment
Project
RFIR_WO_906740_TV03070_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
C 0682
Downstream MH
C 0112
Dir. of Survey
Downstream
Length Surveyed
72.5 ft.
Total Length
72.5 ft.
Structural Index
4
Structural Quick
4B00
Structural Rating
56
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
56
Pipe schematic from manhole C 0682 to C 0112
MH: C 0682MH: C 0112downstream0 ft. AMH - Upstream Manhole, Survey Begins - C 06820 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK3.7 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start72.5 ft. AMH - Downstream Manhole, Survey Ends - C 011272.5 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish72.5 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK

Observation photos (1)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.7 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0AMHC 0682
72.5AMHC 0112
0MWL
3.7FM
72.5FM
72.5MGOCONNECTION AT THE MH 9 OC'LOCK
0MWM
0MGOCONNECTION AT THE MH 3 OC'LOCK

Properties (7)

additional_info
630074080921006
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
1
customer
1
datetime
2021-08-09T04:15:20-07:00
documentation
PROPIPE
is_lateral_inspection
false