Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 13, 2021, 10:07 AM
  • 08 0485_08 0484_08132021_031750.mp4

Date
08/13/2021
W/O
906373
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00019
PipeID
P00543
Time
3:07 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9316
Sewer Name
08 SEPULVEDA-FIGUEROA STREET CONNECTING TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_906373_TV08165_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
36 in.
Upstream MH
08 0485
Downstream MH
08 0484
Dir. of Survey
Downstream
Length Surveyed
221.2 ft.
Total Length
221.2 ft.
Structural Index
4
Structural Quick
4H00
Structural Rating
176
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
176
Pipe schematic from manhole 08 0485 to 08 0484
MH: 08 0485MH: 08 0484downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 04850.2 ft. MWM - Water Mark, 15 %of cross sectional area2.1 ft. RPP - Repair Patch, from 12 to 12 o'clock, within 8 inches of joint: YES3.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start161.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"214.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"221 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish221.2 ft. AMH - Downstream Manhole, Survey Ends - 08 0484

Observation photos (2)

  • Repair Patch, from 12 to 12 o'clock, within 8 inches of joint: YES

    2.1 ft. - Repair Patch, from 12 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
214.6TFC
221FM
161.4TFC
221.2AMH08 0484
0.2MWM
2.1RPP
0MWL
0AMH08 0485
3.2FM

Properties (7)

additional_info
630074081221203
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-08-13T03:07:44-07:00
documentation
PROPIPE
is_lateral_inspection
false