Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 9, 2021, 09:09 AM
  • 29 0146A_29 0146_08092021_021616.mp4

Date
08/09/2021
W/O
906607
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00378
PipeID
P24041
Time
2:09 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9100
Sewer Name
29 REDONDO AVENUE TRUNK
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_906607_TV29061_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
29 0146A
Downstream MH
29 0146
Dir. of Survey
Downstream
Length Surveyed
132.7 ft.
Total Length
132.7 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 29 0146A to 29 0146
MH: 29 0146AMH: 29 0146downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 0146A0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK22.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"64.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES73 ft. H - Hole, at 12 o'clock, within 8 inches of joint: NO132.7 ft. AOC - Drop Connection, Survey Ends - 29 0146

Observation photos (2)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    64.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Hole, at 12 o'clock, within 8 inches of joint: NO

    73 ft. - Hole, at 12 o'clock, within 8 inches of joint: NO

Observations (8)

DistanceCodeObservation
0MWM
0MWL
0AMH29 0146A
22.8TF
64.9FL
73H
0MGOCONNECTION AT THE MH 3 OC'LOCK
132.7AOC29 0146

Properties (7)

additional_info
630074080921002
custom_field_three
CRACKS/ SMALL HOLE
custom_field_two
1
customer
1
datetime
2021-08-09T02:09:27-07:00
documentation
PROPIPE
is_lateral_inspection
false