Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 17, 2021, 04:14 AM
  • 05 0482_05 0481_08162021_215128.mp4

Date
08/16/2021
W/O
906216
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00526
PipeID
P05697
Time
9:14 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9321
Sewer Name
05 STRAWBERRY AVENUE TRUNK
City
HAWTHORNE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_906216_TV05379_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
18 in.
Upstream MH
05 0482
Downstream MH
05 0481
Dir. of Survey
Downstream
Length Surveyed
311.1 ft.
Total Length
311.1 ft.
Structural Index
3
Structural Quick
413K
Structural Rating
178
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
178
Pipe schematic from manhole 05 0482 to 05 0481
MH: 05 0482MH: 05 0481downstream0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 048214.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start24.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"38.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"77 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"92.1 ft. FM - Fracture Multiple, from 07 to 03 o'clock, within 8 inches of joint: YES95.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"122.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"147.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"159.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"196.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"199.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"239.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"245 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"279.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"300.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"306.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish311.1 ft. AMH - Downstream Manhole, Survey Ends - 05 0481

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    14.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 03 o'clock, within 8 inches of joint: YES

    92.1 ft. - Fracture Multiple, from 07 to 03 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
77TF
306.4CM
196.9TF
24.2TF
14.3CM
279.4TF
159.3TF
122.7TF
199.8TFA
311.1AMH05 0481
300.4TF
239.9TF
38.5TF
147.7TF
92.1FM
245TF
0MWL
95.1TF
0MWM
0AMH05 0482

Properties (7)

additional_info
630074081621201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-08-16T21:14:09-07:00
documentation
PROPIPE
is_lateral_inspection
false