Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 26, 2021, 10:45 AM
  • F 0025_F 0024_8262021_035019.mp4

Date
08/26/2021
W/O
0901411
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00033
PipeID
P10115
Time
3:45 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1923
Sewer Name
F JOINT OUTFALL F - UNIT 1
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20210824MDM_JOINT_OUTFALL_F_UNIT_1
Material
Reinforced Concrete Pipe
Shape
Circular
Height
69 in.
Upstream MH
F 0025
Downstream MH
F 0024
Dir. of Survey
Downstream
Length Surveyed
479.6 ft.
Total Length
479.6 ft.
Structural Index
4
Structural Quick
5441
Structural Rating
26
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
30
Pipe schematic from manhole F 0025 to F 0024
MH: F 0025MH: F 0024downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:10AM0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR SPORATIC2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG40.9 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG REBAR292.8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR454.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR479.2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG479.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE479.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR479.6 ft. AMH - Downstream Manhole, Survey Ends - 4:40AM

Observation photos (6)

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR SPORATIC

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR SPORATIC

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG REBAR

    40.9 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR

    292.8 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR

    454.5 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - LONG CIRCUM REBAR

Observations (13)

DistanceCodeObservation
2SRCLONG CIRCUM REBAR SPORATIC
479.2SAMSEVERE AGG
454.5SRCLONG CIRCUM REBAR
0AMH4:10AM
2SSSBLISTERING PEELING CONCRETE
2SAMSEVERE AGG
479.2SSSBLISTERING PEELING CONCRETE
0MWL
292.8SRCLONG CIRCUM REBAR
40.9SRCLONG REBAR
0MWM
479.6AMH4:40AM
479.2SRCLONG CIRCUM REBAR

Properties (6)

custom_field_three
LONG CIRCUM REBAR CORRODED
custom_field_two
2
customer
LACSD
datetime
2021-08-26T03:45:18-07:00
documentation
MARTIN,,OLIVER 111,BARR,RAMIREZ
is_lateral_inspection
false