Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 26, 2021, 09:29 AM
  • F 0026_F OO25_8262021_023228.mp4

Date
08/26/2021
W/O
0901411
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00033
PipeID
P10116
Time
2:29 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1923
Sewer Name
F JOINT OUTFALL F - UNIT 1
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20210824MDM_JOINT_OUTFALL_F_UNIT_1
Material
Reinforced Concrete Pipe
Shape
Circular
Height
69 in.
Upstream MH
F 0026
Downstream MH
F OO25
Dir. of Survey
Downstream
Length Surveyed
249.7 ft.
Total Length
249.7 ft.
Structural Index
5
Structural Quick
5241
Structural Rating
14
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
18
Pipe schematic from manhole F 0026 to F OO25
MH: F 0026MH: F OO25downstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:30AM2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR SPORATIC117.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR249.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR SPORATIC249.2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG249.7 ft. AMH - Downstream Manhole, Survey Ends - 2:50AM

Observation photos (3)

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR SPORATIC

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR SPORATIC

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

    117.1 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

Observations (11)

DistanceCodeObservation
117.1SRCLONG CIRCUM REBAR
0MGOConn. @ Mh, 3 O' Clock. Active
0MGOConn. @ Mh, 9 O' Clock. OPEN
2SAMSEVERE AGG
2SRCLONG CIRCUM REBAR SPORATIC
249.2SRCLONG CIRCUM REBAR SPORATIC
0MWM
0MWL
249.2SAMSEVERE AGG
249.7AMH2:50AM
0AMH2:30AM

Properties (6)

custom_field_three
LONG CIRCUM REBAR CORRODED
custom_field_two
2
customer
LACSD
datetime
2021-08-26T02:29:11-07:00
documentation
MARTIN,,OLIVER 111,BARR,RAMIREZ
is_lateral_inspection
false