Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 25, 2021, 07:19 AM
  • F 0030_F 0029_8252021_012847.mp4

Date
08/25/2021
W/O
0901411
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00033
PipeID
P10120
Time
12:19 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1922
Sewer Name
F JOINT OUTFALL F - UNIT 1
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20210824MDM_JOINT_OUTFALL_F_UNIT_1
Material
Reinforced Concrete Pipe
Shape
Circular
Height
69 in.
Upstream MH
F 0030
Downstream MH
F 0029
Dir. of Survey
Downstream
Length Surveyed
520.7 ft.
Total Length
520.7 ft.
Structural Index
5
Structural Quick
5641
Structural Rating
34
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
38
Pipe schematic from manhole F 0030 to F 0029
MH: F 0030MH: F 0029downstream0 ft. AMH - Upstream Manhole, Survey Begins - 1:30AM0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR11.7 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR35 ft. SRC - Surface Reinforcement Corroded, from 10 to 01 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR BROKEN91.9 ft. SRC - Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR BROKEN111.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active160.1 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR241.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 01 o'clock, within 8 inches of joint: NO, Finish - CIRCUM BROKEN515.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR BROKEN520.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR520.2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG520.7 ft. AMH - Downstream Manhole, Survey Ends - 2:05AM

Observation photos (7)

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

    11.7 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 01 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR BROKEN

    35 ft. - Surface Reinforcement Corroded, from 10 to 01 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR BROKEN

  • Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR BROKEN

    91.9 ft. - Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR BROKEN

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    160.1 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR BROKEN

    515.7 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR BROKEN

Observations (15)

DistanceCodeObservation
35SRCCIRCUM REBAR BROKEN
160.1SRCCIRCUM REBAR
2SAMSEVERE AGG
91.9SRCCIRCUM REBAR BROKEN
0AMH1:30AM
11.7SRCLONG CIRCUM REBAR
520.7AMH2:05AM
520.2SRCLONG CIRCUM REBAR
2SRCLONG CIRCUM REBAR
515.7SRCCIRCUM REBAR BROKEN
0MWM
111.7TFAActive
0MWL
241.1SRCCIRCUM BROKEN
520.2SAMSEVERE AGG

Properties (6)

custom_field_three
LONG CIRCUM REBAR CORRODED & BROKEN
custom_field_two
1
customer
LACSD
datetime
2021-08-25T00:19:44-07:00
documentation
MARTIN,REVELES,OLIVER 111,BARR,
is_lateral_inspection
false