Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 24, 2021, 11:16 AM
  • F 0031_F 0030_8242021_042340.mp4

Date
08/24/2021
W/O
0901411
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00033
PipeID
P10121
Time
4:16 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1922
Sewer Name
F JOINT OUTFALL F - UNIT 1
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20210824MDM_JOINT_OUTFALL_F_UNIT_1
Material
Reinforced Concrete Pipe
Shape
Circular
Height
69 in.
Upstream MH
F 0031
Downstream MH
F 0030
Dir. of Survey
Downstream
Length Surveyed
338.9 ft.
Total Length
338.9 ft.
Structural Index
5
Structural Quick
5841
Structural Rating
44
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
48
Pipe schematic from manhole F 0031 to F 0030
MH: F 0031MH: F 0030downstream0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:20AM0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR BROKEN MISSING2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR BROKEN MISSING16.8 ft. SRC - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: YES - CORRIOSION BEYOUND REBAR21.6 ft. SRC - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR BROKEN37.1 ft. SRC - Surface Reinforcement Corroded, from 09 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR BROKEN HANGING60.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: YES, Start - CORROISON BEYOUND REBAR176 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active184.6 ft. SRC - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR BROKEN HANGING212.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active222.4 ft. SRC - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - BROKEN HANGING REBAR338.4 ft. SRC - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: YES, Finish - CORROSION BEYOUND REBAR338.4 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR BROKEN MISSING338.4 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG338.9 ft. AMH - Downstream Manhole, Survey Ends - 4:50AM

Observations (18)

DistanceCodeObservation
0MWL
184.6SRCCIRCUM REBAR BROKEN HANGING
222.4SRCBROKEN HANGING REBAR
338.9AMH4:50AM
21.6SRCCIRCUM REBAR BROKEN
212.7TFAActive
338.4SRCCORROSION BEYOUND REBAR
2SRCLONG CIRCUM REBAR BROKEN MISSING
2.7SRCLONG CIRCUM REBAR BROKEN MISSING
0AMH4:20AM
338.4SRCLONG CIRCUM REBAR BROKEN MISSING
16.8SRCCORRIOSION BEYOUND REBAR
338.4SAMSEVERE AGG
37.1SRCCIRCUM REBAR BROKEN HANGING
60.3SRCCORROISON BEYOUND REBAR
176TFAActive
0MWM
2SAMSEVERE AGG

Properties (6)

custom_field_three
LONG CIRCUM REBAR CORRODED MISSING
custom_field_two
1
customer
LACSD
datetime
2021-08-24T04:16:09-07:00
documentation
MARTIN,REVELES,BARR,RAMIREZ
is_lateral_inspection
false