Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 24, 2021, 09:53 AM
  • F 0032_F 0031_8242021_032653.mpg

Date
08/24/2021
W/O
0901411
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00033
PipeID
P11207
Time
2:53 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1922
Sewer Name
F JOINT OUTFALL F - UNIT 1
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20210824MDM_JOINT_OUTFALL_F_UNIT_1
Material
Reinforced Concrete Pipe
Shape
Circular
Height
69 in.
Upstream MH
F 0032
Downstream MH
F 0031
Dir. of Survey
Downstream
Length Surveyed
288.7 ft.
Total Length
288.7 ft.
Structural Index
5
Structural Quick
5841
Structural Rating
44
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
48
Pipe schematic from manhole F 0032 to F 0031
MH: F 0032MH: F 0031downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:35AM0 ft. MWL - Water Level, 40 %of cross sectional area8 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR BROKEN MISSING8 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG15.1 ft. SRC - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR CORRODED MISSING93.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR BROKEN139 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR179.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR BROKEN MISSING184.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - CORROSION BEYOUND REBAR261.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE264.4 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - CORRODED BROKEN REBAR276.9 ft. SRC - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - CORROSION BEYOUND REBAR288.2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG288.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR BROKEN MISSING288.7 ft. AMH - Downstream Manhole, Survey Ends - 4:10AM

Observation photos (9)

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR BROKEN MISSING

    8 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR BROKEN MISSING

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    8 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR CORRODED MISSING

    15.1 ft. - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR CORRODED MISSING

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR BROKEN

    93.7 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR BROKEN

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

    139 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, from 09 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR BROKEN MISSING

    179.2 ft. - Surface Reinforcement Corroded, from 09 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR BROKEN MISSING

  • Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - CORROSION BEYOUND REBAR

    184.3 ft. - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - CORROSION BEYOUND REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - CORRODED BROKEN REBAR

    264.4 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - CORRODED BROKEN REBAR

  • Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - CORROSION BEYOUND REBAR

    276.9 ft. - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - CORROSION BEYOUND REBAR

Observations (16)

DistanceCodeObservation
261.3TFACTIVE
93.7SRCCIRCUM REBAR BROKEN
276.9SRCCORROSION BEYOUND REBAR
0MWM
184.3SRCCORROSION BEYOUND REBAR
0AMH3:35AM
8SRCLONG CIRCUM REBAR BROKEN MISSING
139SRCLONG CIRCUM REBAR
288.7AMH4:10AM
8SAMSEVERE AGG
264.4SRCCORRODED BROKEN REBAR
288.2SAMSEVERE AGG
15.1SRCCIRCUM REBAR CORRODED MISSING
0MWL
179.2SRCCIRCUM REBAR BROKEN MISSING
288.2SRCLONG CIRCUM REBAR BROKEN MISSING

Properties (6)

custom_field_three
LONG CIRCUM REBAR CORRODED MISSING
custom_field_two
1
customer
LACSD
datetime
2021-08-24T02:53:16-07:00
documentation
MARTIN,REVELES,BARR,RAMIREZ
is_lateral_inspection
false