Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 10, 2021, 10:59 AM
  • 05 1523_05 1522_08102021_041223.mp4

Date
08/10/2021
W/O
906376
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00528
PipeID
P06745
Time
3:59 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9308
Sewer Name
05 TORRANCE EXTENSION TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
29
Purpose
Routine Assessment
Project
RFIR_WO_906376_TV05309_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
15 in.
Upstream MH
05 1522
Downstream MH
05 1523
Dir. of Survey
Upstream
Length Surveyed
305.2 ft.
Total Length
305.2 ft.
Structural Index
4
Structural Quick
4K00
Structural Rating
240
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
240
Pipe schematic from manhole 05 1522 to 05 1523
MH: 05 1522MH: 05 1523upstream0 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 05 15235.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"50.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"80.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"126.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"159.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"195.1 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"213.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"290.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"301.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start305.2 ft. AMH - Downstream Manhole, Survey Begins - 05 1522305.2 ft. MWL - Water Level, 5 %of cross sectional area305.2 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK305.2 ft. MWM - Water Mark, 25 %of cross sectional area

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
3.6FM
254.8TF
0AMH05 1522
305.2FM
110.1TFA
300.1TF
91.3TF
0MWL
145.3TF
224.6TF
305.2AMH05 1523
14.9TFC
0MGOCONNECTION AT THE MH 9 OC'LOCK
0MWM
178.6TF

Properties (7)

additional_info
630074080921203
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-08-10T03:59:44-07:00
documentation
PROPIPE
is_lateral_inspection
false