Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 27, 2021, 07:35 AM
  • 05 GARDE_D 0051A_8272021_004820.mp4

Date
08/27/2021
W/O
0901829
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00152
PipeID
P09951
Time
12:35 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1925
Sewer Name
D JOINT OUTFALL D - UNIT 2B
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
24
Purpose
Capital Improvement Program Assesment
Project
20210827MDM_JOINT_OUTFALL_D_UNIT_2B
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Upstream MH
05 GARDE
Downstream MH
D 0051A
Dir. of Survey
Downstream
Length Surveyed
5.5 ft.
Total Length
5.5 ft.
Structural Index
5
Structural Quick
5341
Structural Rating
19
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
5
Overall Quick
Overall Rating
24
Pipe schematic from manhole 05 GARDE to D 0051A
MH: 05 GARDEMH: D 0051Adownstream0 ft. MWL - Water Level, 80 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:40AM0 ft. MWM - Water Mark, 80 %of cross sectional area2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR BROKEN MISSING2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR BROKEN MISSING2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR BROKEN MISSING3 ft. MGP - General Photograph - UNUSAL AREA5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR BROKEN MISSING5 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG5.5 ft. MSA - Survey Abandoned - DOWNLEG UPSTREAM SIPHON

Observation photos (6)

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR BROKEN MISSING

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR BROKEN MISSING

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR BROKEN MISSING

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR BROKEN MISSING

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR BROKEN MISSING

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR BROKEN MISSING

  • General Photograph - UNUSAL AREA

    3 ft. - General Photograph - UNUSAL AREA

  • Survey Abandoned - DOWNLEG UPSTREAM SIPHON

    5.5 ft. - Survey Abandoned - DOWNLEG UPSTREAM SIPHON

Observations (11)

DistanceCodeObservation
0MWL
2SRCLONG CIRCUM REBAR BROKEN MISSING
5SRCLONG CIRCUM REBAR BROKEN MISSING
5SAMSEVERE AGG
2SAMSEVERE AGG
5.5MSADOWNLEG UPSTREAM SIPHON
2SRCLONG CIRCUM REBAR BROKEN MISSING
2SRCLONG CIRCUM REBAR BROKEN MISSING
0AMH12:40AM
3MGPUNUSAL AREA
0MWM

Properties (8)

additional_info
DOWNLEG UPSTREAM SIPHON
custom_field_three
LONG CIRCUM REBAR BROKEN MISSING
custom_field_two
1
customer
LACSD
datetime
2021-08-27T00:35:55-07:00
documentation
MARTIN,REVELES,OLIVER 111,RAMIREZ
is_lateral_inspection
false
year_laid