Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 5, 2021, 10:12 AM
  • 29 0455_29 0454_08052021_032842.mp4

Date
08/05/2021
W/O
906729
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00537
PipeID
P24496
Time
3:12 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9097
Sewer Name
29 21ST STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_906729_TV29055_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0455
Downstream MH
29 0454
Dir. of Survey
Downstream
Length Surveyed
316.2 ft.
Total Length
316.2 ft.
Structural Index
3
Structural Quick
443K
Structural Rating
202
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
202
Pipe schematic from manhole 29 0455 to 29 0454
MH: 29 0455MH: 29 0454downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 04553.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start50.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"52.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"146.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"148.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"171.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES204.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES237.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES239 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"244.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"314.6 ft. FM - Fracture Multiple, from 12 to 08 o'clock, within 8 inches of joint: YES316.2 ft. AOC - Drop Connection, Survey Ends - 29 0454316.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (5)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    171.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    204.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    237.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 08 o'clock, within 8 inches of joint: YES

    314.6 ft. - Fracture Multiple, from 12 to 08 o'clock, within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
171.5FM
0MWL
0MWM
314.6FM
3.9CM
204.6FM
0AMH29 0455
148.6TF
146.1TF
316.2AOC29 0454
239TFC
50.4TFC
237.7FM
244.5TF
52.9TFC
316.2CM

Properties (7)

additional_info
630074080421203
custom_field_three
MULTIPLE CRACKS/FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-08-05T03:12:11-07:00
documentation
PROPIPE
is_lateral_inspection
false