Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 4, 2021, 07:13 AM
  • 29 0374_29 0373_08042021_003732.mp4

Date
08/04/2021
W/O
906729
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00537
PipeID
P24411
Time
12:13 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9094
Sewer Name
29 21ST STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_906729_TV29055_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0374
Downstream MH
29 0373
Dir. of Survey
Downstream
Length Surveyed
323.8 ft.
Total Length
323.8 ft.
Structural Index
3
Structural Quick
3V00
Structural Rating
342
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
342
Pipe schematic from manhole 29 0374 to 29 0373
MH: 29 0374MH: 29 0373downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 03742.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - PIPE IS NRCP9.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"11 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"15.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start39.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"52.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"110.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish114.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"118.4 ft. FL - Fracture Longitudinal, at 07 o'clock, within 8 inches of joint: YES152.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"174.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start191.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"242.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"245.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"255.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"323.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish323.8 ft. AMH - Downstream Manhole, Survey Ends - 29 0373 ZOOMED IN323.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    15.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 07 o'clock, within 8 inches of joint: YES

    118.4 ft. - Fracture Longitudinal, at 07 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    174.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
0MWL
152.7TF
114.5TFC
11TF
323.8CM
2.1SAV
323.8AMH29 0373 ZOOMED IN
2.1MGOPIPE IS NRCP
118.4FL
191.5TFA
255.8TFC
245.9TF
110.3CM
0MWM
0AMH29 0374
9.4TF
323.8SAV
15.3CM
39.8TF
52.7TF
174.6CM
242.8TF

Properties (7)

additional_info
630074080321202
custom_field_three
AGGREGATE VISIBLE/MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-08-04T00:13:35-07:00
documentation
PROPIPE
is_lateral_inspection
false