- Date
- 08/10/2021
- W/O
- 906709
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00583
- PipeID
- P18373
- Time
- 1:47 AM
- Certificate
- U-0720-70309212
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K9227
- Sewer Name
- 14 TRUNK "F"
- City
- LANCASTER
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 14
- Page No.
- 16
- Purpose
- Routine Assessment
- Project
- RFIR_WO_906709_TV14076_AUG2021
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 21 in.
- Width
- 21 in.
- Upstream MH
- 14 0306A
- Downstream MH
- 14 0306
- Dir. of Survey
- Downstream
- Length Surveyed
- 349.4 ft.
- Total Length
- 349.4 ft.
- Structural Index
- 3
- Structural Quick
- 513M
- Structural Rating
- 347
- O&M Index
- 2
- O&M Quick
- 2M00
- O&M Rating
- 138
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 485
Pipe schematic from manhole 14 0306A to 14 0306 Observation photos (4)

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

6.4 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

339.7 ft. - Surface Reinforcement Visible, from 01 to 05 o'clock, within 8 inches of joint: YES