Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 12, 2017, 05:26 AM
  • 22 1015_22 1014_11102017_222635.mp4

Date
10/11/2017
W/O
663288
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00819
PipeID
P17384
Time
10:26 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5015
Sewer Name
22 LORAINE TRUNK
City
GLENDORA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
13
Purpose
Routine Assessment
Project
WO_663288_TV22159_OCT2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 1015
Downstream MH
22 1014
Dir. of Survey
Downstream
Length Surveyed
392.9 ft.
Total Length
392.9 ft.
Structural Index
3
Structural Quick
3O00
Structural Rating
234
O&M Index
2
O&M Quick
4333
O&M Rating
40
Overall Index
3
Overall Quick
Overall Rating
274
Pipe schematic from manhole 22 1015 to 22 1014
MH: 22 1015MH: 22 1014downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 10150 ft. MWM - Water Mark, 25 %of cross sectional area2.1 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAG COAT15.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"69.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"147.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"180.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"220.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"252.3 ft. RFJ - Roots Fine Joint, at 07 o'clock, within 8 inches of joint: YES261.5 ft. RMC - Roots Medium Connection, from 02 to 05 o'clock, 15 %, within 8 inches of joint: YES264.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"264.2 ft. RBL - Roots Ball Lateral, at 02 o'clock, 95 %285.7 ft. RFJ - Roots Fine Joint, from 07 to 09 o'clock, within 8 inches of joint: YES302.3 ft. RFJ - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Start319.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"319.3 ft. RBL - Roots Ball Lateral, at 02 o'clock, 75 %319.3 ft. RMC - Roots Medium Connection, from 02 to 05 o'clock, 15 %, within 8 inches of joint: NO371.8 ft. RMC - Roots Medium Connection, from 02 to 05 o'clock, 20 %, within 8 inches of joint: NO371.8 ft. RBL - Roots Ball Lateral, at 02 o'clock, 95 %371.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"387.4 ft. RFJ - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish390.2 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish392.9 ft. AMH - Downstream Manhole, Survey Ends - 22 1014

Observation photos (5)

  • Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 07 o'clock, within 8 inches of joint: YES

    252.3 ft. - Roots Fine Joint, at 07 o'clock, within 8 inches of joint: YES

  • Roots Medium Connection, from 02 to 05 o'clock, 15 %, within 8 inches of joint: YES

    261.5 ft. - Roots Medium Connection, from 02 to 05 o'clock, 15 %, within 8 inches of joint: YES

  • Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    302.3 ft. - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Connection, from 02 to 05 o'clock, 20 %, within 8 inches of joint: NO

    371.8 ft. - Roots Medium Connection, from 02 to 05 o'clock, 20 %, within 8 inches of joint: NO

Observations (25)

DistanceCodeObservation
261.5RMC
319.3TF
69.9TF
2.1SAP
371.8RMC
387.4RFJ
319.3RBL
2.1MGOMAG COAT
15.7TFA
264.2TF
392.9AMH22 1014
0MWL
147.4TF
180.9TFA
285.7RFJ
371.8RBL
0AMH22 1015
220.3TFC
390.2SAP
264.2RBL
252.3RFJ
0MWM
319.3RMC
371.8TF
302.3RFJ

Properties (6)

additional_info
SC345175
custom_field_two
2
customer
LACSD
datetime
2017-10-11T22:26:25-07:00
documentation
PROPIPE
is_lateral_inspection
false