Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 6, 2017, 10:51 AM
  • 05 0885_05 0144 _06102017_035200.mp4

Date
10/06/2017
W/O
663034
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00512
PipeID
P06116
Time
3:51 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5008
Sewer Name
05 RAYMOND AVENUE TRUNK
City
HAWTHRONE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
WO_663034_TV05096_OCT2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
05 0885
Downstream MH
05 0144
Dir. of Survey
Downstream
Length Surveyed
166.8 ft.
Total Length
166.8 ft.
Structural Index
3
Structural Quick
3222
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 05 0885 to 05 0144
MH: 05 0885MH: 05 0144downstream0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK, ACTIVE0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK CAPPED0 ft. AMH - Upstream Manhole, Survey Begins - 05 08850 ft. MWL - Water Level, 5 %of cross sectional area53.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"56.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"79 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"81.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"100.6 ft. CS - Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES103.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"106.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"120.6 ft. CM - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES129.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"131.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"135.7 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES151 ft. CM - Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES154.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"156.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"166.8 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK166.8 ft. AMH - Downstream Manhole, Survey Ends - 05 0144

Observation photos (4)

  • Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES

    100.6 ft. - Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    120.6 ft. - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    135.7 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

    151 ft. - Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
106.5TF
151CM
120.6CM
0MWM
56.3TFC
0MGOCONNECTION AT MH 9 O'CLOCK, ACTIVE
100.6CS
0MGOCONNECTION AT MH 3 O'CLOCK CAPPED
129.4TF
81.4TFC
79TF
0AMH05 0885
53.7TFC
166.8MGOCONNECTION AT MH 9 O'CLOCK
156.8TFC
154.6TF
0MWL
135.7CL
166.8AMH05 0144
131.9TF
103.9TFC

Properties (6)

additional_info
SC346168
custom_field_two
4
customer
LACSD
datetime
2017-10-06T03:51:37-07:00
documentation
PROPIPE
is_lateral_inspection
false