Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 3, 2017, 05:16 AM
  • H 0001_B 0070B_02102017_222048.mp4

Date
10/02/2017
W/O
658098
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00115
PipeID
P09445
Time
10:16 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4898
Sewer Name
B JOINT OUTFALL B - UNIT 9C
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
09
Purpose
Routine Assessment
Project
WO_658098_TV08061_SEP2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
90 in.
Width
90 in.
Upstream MH
B 0070B
Downstream MH
H 0001
Dir. of Survey
Upstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole B 0070B to H 0001
MH: B 0070BMH: H 0001upstream0 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES0 ft. AMH - Upstream Manhole, Survey Ends - H 00010 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES2 ft. MWM - Water Mark, 30 %of cross sectional area2.1 ft. AMH - Downstream Manhole, Survey Begins - B 0070B2.1 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (6)

DistanceCodeObservation
0AMHB 0070B
0MWL
2.1SAP
2.1AMHH 0001
0.1MWM
2.1SRV

Properties (7)

additional_info
SC346158
custom_field_two
2
customer
LACSD
datetime
2017-10-02T22:16:26-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
33875