Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 25, 2017, 05:30 AM
  • 22 1075_22 1074 _02082017_082835.mp4

Date
07/24/2017
W/O
646476
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00812
PipeID
P17448
Time
10:30 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4666
Sewer Name
22 IRWINDALE TRUNK, SECTS 2,3,4,&5
City
IRWINDALE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
18
Purpose
Routine Assessment
Project
WO_646476_TV22042_JUL2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 1075
Downstream MH
22 1074
Dir. of Survey
Downstream
Length Surveyed
401.5 ft.
Total Length
401.5 ft.
Structural Index
3
Structural Quick
413O
Structural Rating
244
O&M Index
2
O&M Quick
2O00
O&M Rating
160
Overall Index
3
Overall Quick
Overall Rating
404
Pipe schematic from manhole 22 1075 to 22 1074
MH: 22 1075MH: 22 1074downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 10750 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - RESUMING VIDEO1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.4 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"74 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES85.8 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"88.3 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"153.1 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"232.8 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"235.3 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"315.4 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"385.3 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"387.9 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"401.5 ft. AMH - Downstream Manhole, Survey Ends - 22 1074401.5 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish401.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    1 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    74 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
315.4TFC
387.9TFC
3.2CM
1DAGS
0AMH22 1075
88.3TFC
153.1TFC
0MWM
0MWL
401.5AMH22 1074
385.3TFC
74FM
235.3TFC
6.4TFC
85.8TFC
0MGORESUMING VIDEO
401.5DAGS
232.8TF
401.5CM

Properties (6)

additional_info
SC345604
custom_field_two
3
customer
LACSD
datetime
2017-07-24T22:30:58-07:00
documentation
PROPIPE
is_lateral_inspection
false