Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 2, 2017, 09:41 AM
  • J 0243_J 0242_1122017_030728.mp4

Date
11/02/2017
W/O
0624519
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00057
PipeID
P11489
Time
2:41 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0667
Sewer Name
J JOINT OUTFALL J - UNIT 1E
City
PALO VERDES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
46
Purpose
Routine Assessment
Project
20171102MDM_JOINT_OUTFALL_J_UNIT_1E
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
J 0242
Downstream MH
J 0243
Dir. of Survey
Upstream
Length Surveyed
492.9 ft.
Total Length
492.9 ft.
Structural Index
4
Structural Quick
5B36
Structural Rating
91
O&M Index
4
O&M Quick
5141
O&M Rating
11
Overall Index
4
Overall Quick
Overall Rating
102
Pipe schematic from manhole J 0242 to J 0243
MH: J 0242MH: J 0243upstream0 ft. AMH - Upstream Manhole, Survey Ends - 4:15AM0.7 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - CIRCUM LONG REBAR0.7 ft. MGO - General Observation - MH CONN 9:00 ACTIVE0.7 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SP[ORATIC0.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE5.4 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES5.7 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM LONG REBAR5.7 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM & LONG REBAR9.9 ft. SRC - Surface Reinforcement Corroded, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR22 ft. DSGV - Deposits Settled Gravel, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, - SLUDGE27.2 ft. SRV - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: YES - CIRCUM34.2 ft. SRV - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM47.2 ft. SRV - Surface Reinforcement Visible, from 09 to 10 o'clock, within 8 inches of joint: YES, Finish - CIRCUM51.6 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC51.6 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG51.6 ft. MWM - Water Mark, 40 %of cross sectional area51.6 ft. MWL - Water Level, 20 %of cross sectional area51.6 ft. SRV - Surface Reinforcement Visible, from 09 to 10 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR51.6 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE51.6 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE89 ft. MGO - General Observation - MAG COAT 80% FINISH89 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC89 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE89 ft. MWL - Water Level, 40 %of cross sectional area89 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE89 ft. MWM - Water Mark, 80 %of cross sectional area109.3 ft. SAV - Surface Aggregate Visible, from 08 to 09 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG109.3 ft. SAV - Surface Aggregate Visible, from 03 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG109.3 ft. MWM - Water Mark, 60 %of cross sectional area118 ft. SRV - Surface Reinforcement Visible, from 02 to 04 o'clock, within 8 inches of joint: YES, Finish - CIRCUM118 ft. SRV - Surface Reinforcement Visible, from 08 to 10 o'clock, within 8 inches of joint: YES, Finish - CIRCUM140.3 ft. SRV - Surface Reinforcement Visible, from 02 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR154.6 ft. SRV - Surface Reinforcement Visible, from 08 to 10 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR166 ft. SRV - Surface Reinforcement Visible, at 02 o'clock, within 8 inches of joint: YES, Finish - LONG REBAR166.4 ft. SRV - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR169.3 ft. SRV - Surface Reinforcement Visible, at 02 o'clock, within 8 inches of joint: YES, Start - LONG REBAR246.9 ft. SAV - Surface Aggregate Visible, from 03 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC246.9 ft. SAV - Surface Aggregate Visible, from 08 to 09 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC251.1 ft. SAV - Surface Aggregate Visible, from 02 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC309.3 ft. SRV - Surface Reinforcement Visible, from 09 to 10 o'clock, within 8 inches of joint: NO - CIRCUM REBAR311.3 ft. SRV - Surface Reinforcement Visible, from 09 to 10 o'clock, within 8 inches of joint: NO - CIRCUM REBAR414.1 ft. SAV - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG469 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE490.9 ft. MGO - General Observation - MAG COAT 80% START 8:00 TO 4:00490.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE492.9 ft. MWM - Water Mark, 20 %of cross sectional area492.9 ft. AMH - Downstream Manhole, Survey Begins - 3:05AM492.9 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (22)

  • General Observation - MAG COAT 80% START 8:00 TO 4:00

    2 ft. - General Observation - MAG COAT 80% START 8:00 TO 4:00

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

    23.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

  • Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG

    78.8 ft. - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Surface Reinforcement Visible, from 09 to 10 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    181.6 ft. - Surface Reinforcement Visible, from 09 to 10 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 09 to 10 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    183.6 ft. - Surface Reinforcement Visible, from 09 to 10 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Aggregate Visible, from 03 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    246 ft. - Surface Aggregate Visible, from 03 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Aggregate Visible, from 08 to 09 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    246 ft. - Surface Aggregate Visible, from 08 to 09 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Reinforcement Visible, at 02 o'clock, within 8 inches of joint: YES, Start - LONG REBAR

    323.6 ft. - Surface Reinforcement Visible, at 02 o'clock, within 8 inches of joint: YES, Start - LONG REBAR

  • Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    326.5 ft. - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 08 to 10 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    338.3 ft. - Surface Reinforcement Visible, from 08 to 10 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Visible, from 02 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    352.6 ft. - Surface Reinforcement Visible, from 02 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Water Mark, 60 %of cross sectional area

    383.6 ft. - Water Mark, 60 %of cross sectional area

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    403.9 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    403.9 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Reinforcement Visible, from 09 to 10 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    441.3 ft. - Surface Reinforcement Visible, from 09 to 10 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM

    458.7 ft. - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: YES - CIRCUM

    465.7 ft. - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: YES - CIRCUM

  • Surface Reinforcement Corroded, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    483 ft. - Surface Reinforcement Corroded, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM LONG REBAR

    487.2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM LONG REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM & LONG REBAR

    487.2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM & LONG REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES

    487.5 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (48)

DistanceCodeObservation
483SRCCIRCUM REBAR
465.7SRVCIRCUM
441.3SAVSEVERE AGG SPORATIC
383.6SAVSEVERE AGG
441.3SAVSEVERE AGG
383.6SAVSEVERE AGG
78.8SAVSEVERE AGG
470.9DSGVSLUDGE
0MWM
23.9SSSBLISTERING PEELING CONCRETE
441.3MWM
492.2SRCCIRCUM LONG REBAR
441.3MWL
0AMH3:05AM
338.3SRVCIRCUM REBAR
181.6SRVCIRCUM REBAR
403.9MGOMAG COAT 80% FINISH
492.9AMH4:15AM
492.2MGOMH CONN 9:00 ACTIVE
441.3SRVCIRCUM REBAR
0MWL
403.9SAVSEVERE AGG SPORATIC
246SAVSEVERE AGG SPORATIC
403.9SSSBLISTERING PEELING CONCRETE
246SAVSEVERE AGG SPORATIC
441.3SSSBLISTERING PEELING CONCRETE
403.9MWL
383.6MWM
487.2SRCCIRCUM LONG REBAR
487.5SRC
492.2SAVSEVERE AGG SP[ORATIC
445.7SRVCIRCUM
352.6SRVCIRCUM REBAR
487.2SRCCIRCUM & LONG REBAR
2MGOMAG COAT 80% START 8:00 TO 4:00
492.2SSSBLISTERING PEELING CONCRETE
374.9SRVCIRCUM
2SSSBLISTERING PEELING CONCRETE
326.5SRVCIRCUM REBAR
183.6SRVCIRCUM REBAR
403.9SSSBLISTERING PEELING CONCRETE
441.3SSSBLISTERING PEELING CONCRETE
403.9MWM
374.9SRVCIRCUM
323.6SRVLONG REBAR
241.8SAVSEVERE AGG SPORATIC
458.7SRVCIRCUM
326.9SRVLONG REBAR

Properties (6)

custom_field_three
CIRCUM & LONG REBAR CORRODED
custom_field_two
2
customer
LACSD
datetime
2017-11-02T02:41:35-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false