Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 12, 2021, 05:04 AM
  • 22 0330_22 0329_08112021_222221.mp4

Date
08/11/2021
W/O
906759
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00795
PipeID
P16617
Time
10:04 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9115
Sewer Name
22 CAMERON RELIEF TRUNK
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_906759_TV22188_AUG2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
22 0330
Downstream MH
22 0329
Dir. of Survey
Downstream
Length Surveyed
559.9 ft.
Total Length
559.9 ft.
Structural Index
4
Structural Quick
5231
Structural Rating
15
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
15
Pipe schematic from manhole 22 0330 to 22 0329
MH: 22 0330MH: 22 0329downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 03302.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAG COAT2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start134 ft. SRV - Surface Reinforcement Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start288.3 ft. SRV - Surface Reinforcement Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish295.7 ft. SRV - Surface Reinforcement Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start557 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish557 ft. SRV - Surface Reinforcement Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish557 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish559.9 ft. AMH - Downstream Manhole, Survey Ends - 22 0329

Observation photos (5)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT

    2.1 ft. - General Observation - MAG COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    134 ft. - Surface Reinforcement Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    295.7 ft. - Surface Reinforcement Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0MWM
559.9AMH22 0329
2.1SAV
0MWL
557SAV
2.1MGOMAG COAT
288.3SRV
2.1SSS
134SRV
557SRV
0AMH22 0330
295.7SRV
557SSS

Properties (7)

additional_info
630138081121201
custom_field_three
REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2021-08-11T22:04:22-07:00
documentation
PRO PIPE
is_lateral_inspection
false