Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 12, 2021, 07:51 AM
  • 22 0326_22 0325_08122021_011347.mp4

Date
08/12/2021
W/O
906759
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00795
PipeID
P16613
Time
12:51 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9115
Sewer Name
22 CAMERON RELIEF TRUNK
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
35
Purpose
Routine Assessment
Project
RFIR_WO_906759_TV22188_AUG2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
22 0326
Downstream MH
22 0325
Dir. of Survey
Downstream
Length Surveyed
627.3 ft.
Total Length
627.3 ft.
Structural Index
4
Structural Quick
5331
Structural Rating
20
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
24
Pipe schematic from manhole 22 0326 to 22 0325
MH: 22 0326MH: 22 0325downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 03260 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. MGO - General Observation - MAG COAT2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start196.3 ft. SRV - Surface Reinforcement Visible, from 01 to 04 o'clock, within 8 inches of joint: NO201.6 ft. SRV - Surface Reinforcement Visible, from 08 to 10 o'clock, within 8 inches of joint: YES261.9 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"362.7 ft. SRV - Surface Reinforcement Visible, at 04 o'clock, within 8 inches of joint: NO403.4 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"532 ft. TBC - Tap Break-In Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"612.9 ft. TBC - Tap Break-In Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"624.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish624.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish627.3 ft. AMH - Downstream Manhole, Survey Ends - 22 0325

Observation photos (10)

  • General Observation - MAG COAT

    2 ft. - General Observation - MAG COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 01 to 04 o'clock, within 8 inches of joint: NO

    196.3 ft. - Surface Reinforcement Visible, from 01 to 04 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 08 to 10 o'clock, within 8 inches of joint: YES

    201.6 ft. - Surface Reinforcement Visible, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"

    261.9 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"

  • Surface Reinforcement Visible, at 04 o'clock, within 8 inches of joint: NO

    362.7 ft. - Surface Reinforcement Visible, at 04 o'clock, within 8 inches of joint: NO

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"

    403.4 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"

    532 ft. - Tap Break-In Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"

    612.9 ft. - Tap Break-In Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"

Observations (17)

DistanceCodeObservation
0MWM
624.6SAV
627.3AMH22 0325
0AMH22 0326
201.6SRV
362.7SRV
2MGOMAG COAT
2SSS
612.9TBC
0MGOCONNECTION AT MH 3 O'CLOCK
2SAV
196.3SRV
532TBC
624.6SSS
0MWL
261.9TB
403.4TB

Properties (7)

additional_info
630138081121201
custom_field_three
REINFORCEMENT VISIBLE, SPALLING
custom_field_two
2
customer
1
datetime
2021-08-12T00:51:03-07:00
documentation
PRO PIPE
is_lateral_inspection
false