Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 15, 2018, 10:16 AM
  • 22 0963_22 0962_15082018_032944.mp4

Date
08/15/2018
W/O
717737
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00790
PipeID
P17333
Time
3:16 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5901
Sewer Name
22 BASE LINE TRUNK
City
GLENDORA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
12
Purpose
Routine Assessment
Project
WO_717737_TV22002_AUG2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0963
Downstream MH
22 0962
Dir. of Survey
Downstream
Length Surveyed
342.8 ft.
Total Length
342.8 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
201
O&M Index
2
O&M Quick
2L00
O&M Rating
134
Overall Index
3
Overall Quick
Overall Rating
335
Pipe schematic from manhole 22 0963 to 22 0962
MH: 22 0963MH: 22 0962downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 22 09630 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4 ft. MGO - General Observation - MAG COATING THROUGHOUT 50%27 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"46.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"76.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"96.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"128.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"147.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"180.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"197 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"228.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"245.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"289.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"297.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"339.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish339.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish339.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE342.8 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK342.8 ft. AMH - Downstream Manhole, Survey Ends - 22 0962

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (24)

DistanceCodeObservation
2SAV
228.6TFC
147.9TFC
0MWL
342.8MGOACTIVE CONNECTION AT MH 9 O'CLOCK
46.5TFC
2DAGS
128.3TFC
96.9TFC
339.3SAV
339.3DAGS
180.8TFA
0MGOCOCKROACHES IN MANHOLE
297.5TFC
76.1TFC
289.8TFC
245.3TFC
342.8AMH22 0962
4MGOMAG COATING THROUGHOUT 50%
0AMH22 0963
27TFC
0MWM
197TFC
339.3MGOCOCKROACHES IN MANHOLE

Properties (6)

additional_info
SC364770
custom_field_two
3
customer
LACSD
datetime
2018-08-15T03:16:16-07:00
documentation
PRO PIPE
is_lateral_inspection
false