Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 7, 2018, 03:30 PM
  • D 0082_D 0081_972018_084249.mp4

Date
09/07/2018
W/O
0726351
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00154
PipeID
P09982
Time
8:30 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7803
Sewer Name
D JOINT OUTFALL D - UNIT 4
City
HAWTHORNE
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
20
Purpose
Capital Improvement Program Assesment
Project
20180906DF_JOINT_OUTFALL_D_UNIT_4
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Upstream MH
D 0082
Downstream MH
D 0081
Dir. of Survey
Downstream
Length Surveyed
9 ft.
Total Length
9 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
5
O&M Quick
5141
O&M Rating
9
Overall Index
4
Overall Quick
Overall Rating
19
Pipe schematic from manhole D 0082 to D 0081
MH: D 0082MH: D 0081downstream0 ft. MWL - Water Level, 100 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 8:33 AM0 ft. MWM - Water Mark, 100 %of cross sectional area2 ft. LD - Alignment Down, 45 %2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.5 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 50% MAG9 ft. MSA - Survey Abandoned - LOW WATER FLOW9 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish9 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 50% MAG

Observation photos (5)

  • Water Mark, 100 %of cross sectional area

    0 ft. - Water Mark, 100 %of cross sectional area

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 50% MAG

    2.5 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 50% MAG

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

    9 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observations (13)

DistanceCodeObservation
9MSALOW WATER FLOW
9SRV
9SSS
9SAV
2LD
0MWL
0AMH8:33 AM
9SZ50% MAG
2.5SSS
2SRV
0MWM
2.5SAV
2.5SZ50% MAG

Properties (6)

additional_info
VIEW OF THE DOWNLEG FROM U/S MH
custom_field_two
5
customer
LACSD
datetime
2018-09-07T08:30:59-07:00
documentation
FRANKLIN, VENDRYES
is_lateral_inspection
false