Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 11, 2021, 07:55 AM
  • 08 0638_08 0341_08112021_011243.mp4

Date
08/11/2021
W/O
906744
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00003
PipeID
P00392
Time
12:55 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9311
Sewer Name
08 DAVIDSON CITY TRUNK, SECTS 1,2,&3
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
15
Purpose
Routine Assessment
Project
WO_906744_TV08104_AUG2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
12 in.
Upstream MH
08 0638
Downstream MH
08 0341
Dir. of Survey
Downstream
Length Surveyed
330.6 ft.
Total Length
330.6 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
330
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
330
Pipe schematic from manhole 08 0638 to 08 0341
MH: 08 0638MH: 08 0341downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 06380 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start312 ft. TS - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"319.8 ft. TS - Tap Saddle, at 10 o'clock, -, within 8 inches of joint: NO, 6"330.6 ft. AMH - Downstream Manhole, Survey Ends - 08 0341330.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish330.6 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK330.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    312 ft. - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Saddle, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    319.8 ft. - Tap Saddle, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (11)

DistanceCodeObservation
2.6SAP
330.6AMH08 0341
0AMH08 0638
0MWL
2.6SSS
330.6SAP
0MWM
319.8TS
330.6MGOCONNECTION AT THE MH 9 OC'LOCK
312TS
330.6SSS

Properties (7)

additional_info
630074081021203
custom_field_three
AGGREGATE PROJECTING/SPALLING
custom_field_two
2
customer
1
datetime
2021-08-11T00:55:46-07:00
documentation
PROPIPE
is_lateral_inspection
false