Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 23, 2021, 09:14 AM
  • 15 0001_H 0717_07232021_022602.mp4

Date
07/23/2021
W/O
901521
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00941
PipeID
P11126
Time
2:14 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8550
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
LA PUENTE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
RFIR_WO_901521_TV22077_JUL2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
25 in.
Width
25 in.
Upstream MH
H 0717
Downstream MH
15 0001
Dir. of Survey
Upstream
Length Surveyed
289.9 ft.
Total Length
289.9 ft.
Structural Index
3
Structural Quick
3J2J
Structural Rating
285
O&M Index
2
O&M Quick
412K
O&M Rating
120
Overall Index
2
Overall Quick
Overall Rating
405
Pipe schematic from manhole H 0717 to 15 0001
MH: H 0717MH: 15 0001upstream0 ft. AMH - Upstream Manhole, Survey Ends - 15 00011.1 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/OPEN2.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish280.4 ft. LR - Alignment Right, 20 %286.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start287.9 ft. MGO - General Observation - 65% MAG COAT287.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start287.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start289.9 ft. MWM - Water Mark, 25 %of cross sectional area289.9 ft. AMH - Downstream Manhole, Survey Begins - H 0717 NON STRUCTURE289.9 ft. MWL - Water Level, 20 %of cross sectional area

Observation photos (3)

  • General Observation - 65% MAG COAT

    2 ft. - General Observation - 65% MAG COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Alignment Right, 20 %

    9.5 ft. - Alignment Right, 20 %

Observations (13)

DistanceCodeObservation
287SAV
9.5LR
288.8MGOCONN @ MH 3 O'CLOCK/OPEN
287.2SSS
0MWM
2MGO65% MAG COAT
0AMHH 0717 NON STRUCTURE
287DAGS
3.1SSS
2SAV
0MWL
2DAGS
289.9AMH15 0001

Properties (6)

custom_field_three
SPALLING, MAG COAT
custom_field_two
3
customer
1
datetime
2021-07-23T02:14:00-07:00
documentation
PRO PIPE
is_lateral_inspection
false