Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 19, 2014, 05:09 PM
  • 14 0367_14 0366_20141219_110027.mp4

Date
12/19/2014
W/O
479094
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00581
PipeID
P18444
Time
9:09 AM
Certificate
U507-03-3386
System Owner
LACSD
Date Cleaned
12/19/14
Pre-Cleaning
No Pre-Cleaning
Media Label
K2160
Sewer Name
14 TRUNK "E"
City
LANCASTER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
07
Purpose
Infiltration/Inflow Investigation
Project
WO_479094_2014NOVEMBER_U
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
12 in.
Upstream MH
14 0366
Downstream MH
14 0367
Dir. of Survey
Upstream
Length Surveyed
400.9 ft.
Total Length
400.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
3200
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 14 0366 to 14 0367
MH: 14 0366MH: 14 0367upstream0 ft. AMH - Upstream Manhole, Survey Ends - 14 0367 (10:59)0 ft. DSF - Deposits Settled Fine, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: NO, Finish31 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"55.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"79.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"103.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"131.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"156 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"184 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"207.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"232 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4" - COULD POSSIBLY BE CAPPED232 ft. RML - Roots Medium Lateral, from 07 to 10 o'clock, 15 %, within 8 inches of joint: NO256.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"280.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"304 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"330.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"357.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"373.5 ft. DSF - Deposits Settled Fine, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start400.9 ft. AMH - Downstream Manhole, Survey Begins - 14 0366 (09:09)400.9 ft. MWL - Water Level, 15 %of cross sectional area

Observation photos (3)

  • Downstream Manhole, Survey Begins - 14 0366 (09:09)

    0 ft. - Downstream Manhole, Survey Begins - 14 0366 (09:09)

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4" - COULD POSSIBLY BE CAPPED

    168.9 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4" - COULD POSSIBLY BE CAPPED

  • Upstream Manhole, Survey Ends - 14 0367 (10:59)

    400.9 ft. - Upstream Manhole, Survey Ends - 14 0367 (10:59)

Observations (20)

DistanceCodeObservation
0AMH14 0366 (09:09)
345.8TFC
168.9TFCOULD POSSIBLY BE CAPPED
216.9TFC
168.9RML
0MWL
27.4DSF
369.9TFC
193.4TFC
400.9AMH14 0367 (10:59)
269TFC
400.9DSF
297.1TFC
43.7TFC
244.9TFC
96.9TFC
70.4TFC
120.6TFC
144.5TFC
321.3TFC

Properties (6)

custom_field_two
4
customer
LACSD
datetime
2014-12-19T09:09:00-08:00
documentation
PRO-PIPE
is_lateral_inspection
false
year_laid