Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 11, 2021, 07:31 AM
  • 14 0382_14 0381A_08112021_003939.mp4

Date
08/11/2021
W/O
896585
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00581
PipeID
P18462
Time
12:31 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9228
Sewer Name
14 TRUNK "E"
City
LANCASTER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_896585_TV14025_JUN2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0382
Downstream MH
14 0381A
Dir. of Survey
Downstream
Length Surveyed
166 ft.
Total Length
166 ft.
Structural Index
3
Structural Quick
3F2F
Structural Rating
165
O&M Index
4
O&M Quick
514E
O&M Rating
125
Overall Index
3
Overall Quick
Overall Rating
290
Pipe schematic from manhole 14 0382 to 14 0381A
MH: 14 0382MH: 14 0381Adownstream0 ft. MWL - Water Level, 70 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 03822.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.5 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start14 ft. MCU - Camera Underwater, Start19.3 ft. MWL - Water Level, 80 %of cross sectional area166 ft. MSA - Survey Abandoned - DUE TO DEBRIS.166 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish166 ft. MCU - Camera Underwater, Finish166 ft. DSZ - Deposits Settled Other, 40 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES - DEBRIS166 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Settled Other,  40 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES - DEBRIS

    166 ft. - Deposits Settled Other, 40 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES - DEBRIS

Observations (11)

DistanceCodeObservation
2.5SSS
166MSADUE TO DEBRIS.
0MWL
166SAP
166MCU
2.5SAP
19.3MWL
166DSZDEBRIS
0AMH14 0382
14MCU
166SSS

Properties (7)

additional_info
630069081021201
custom_field_three
ABANDONED DUE TO DEBRIS/CAMERA UNDER WATER
custom_field_two
5
customer
1
datetime
2021-08-11T00:31:08-07:00
documentation
PRO PIPE
is_lateral_inspection
false