Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 10, 2014, 08:47 AM
  • 14 0329_14 0328_10122014_010959.mp4

Date
12/10/2014
W/O
476827
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00583
PipeID
P18402
Time
12:47 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K1922
Sewer Name
14 TRUNK "F"
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
10
Purpose
Routine Assessment
Project
WO_476827_TV14027_2014NOVEMBER
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
12 in.
Upstream MH
14 0329
Downstream MH
14 0328
Dir. of Survey
Downstream
Length Surveyed
393.1 ft.
Total Length
393.1 ft.
Structural Index
3
Structural Quick
3O22
Structural Rating
238
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
238
Pipe schematic from manhole 14 0329 to 14 0328
MH: 14 0329MH: 14 0328downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 03292 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start27.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"51.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"76.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"104.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"128.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"153.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"177.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"192.1 ft. SSS - Surface Spalling, from 10 to 12 o'clock, within 8 inches of joint: YES196.2 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES202.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"226.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"254.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"279.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"303.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"327.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"352.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"368.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"391.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish393.1 ft. AMH - Downstream Manhole, Survey Ends - 14 0328

Observation photos (22)

  • Water Mark, 15 %of cross sectional area

    0 ft. - Water Mark, 15 %of cross sectional area

  • Water Level, 5 %of cross sectional area

    0 ft. - Water Level, 5 %of cross sectional area

  • Upstream Manhole, Survey Begins - 14 0329

    0 ft. - Upstream Manhole, Survey Begins - 14 0329

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    27.9 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    51.8 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    76.2 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    104.6 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    128.6 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    153.5 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    177.9 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Surface Spalling, from 10 to 12 o'clock, within 8 inches of joint: YES

    192.1 ft. - Surface Spalling, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES

    196.2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    202.2 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    226.5 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    254.9 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    279.2 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    303.3 ft. - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    327.8 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    352.1 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    368.6 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Downstream Manhole, Survey Ends - 14 0328

    393.1 ft. - Downstream Manhole, Survey Ends - 14 0328

Observations (23)

DistanceCodeObservation
177.9TFC
192.1SSS
327.8TFC
76.2TFC
352.1TFC
128.6TFC
393.1AMH14 0328
226.5TFC
202.2TFC
153.5TFC
391.1SAP
279.2TFC
27.9TFC
0MWM
196.2SSS
51.8TFC
0MWL
2SAP
0AMH14 0329
254.9TFC
303.3TFA
368.6TFC
104.6TFC

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2014-12-10T00:47:16-08:00
documentation
PRO PIPE
is_lateral_inspection
false