Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 10, 2014, 10:41 AM
  • 14 0330_14 0329A_10122014_025327.mp4

Date
12/10/2014
W/O
476827
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00583
PipeID
P18404
Time
2:41 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K1922
Sewer Name
14 TRUNK "F"
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
10
Purpose
Routine Assessment
Project
WO_476827_TV14027_2014NOVEMBER
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
12 in.
Upstream MH
14 0329A
Downstream MH
14 0330
Dir. of Survey
Upstream
Length Surveyed
250.3 ft.
Total Length
250.3 ft.
Structural Index
3
Structural Quick
3I2G
Structural Rating
229
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
231
Pipe schematic from manhole 14 0329A to 14 0330
MH: 14 0329AMH: 14 0330upstream0 ft. AMH - Upstream Manhole, Survey Ends - 14 03302.6 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish2.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish27.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"31.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"76.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"100.1 ft. OBM - Obstacles Pipe Material, 10 %of cross sectional area, from 06 to 08 o'clock100.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"128.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"153.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"176 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"201.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"205.1 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start224.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"247.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start250.3 ft. MWM - Water Mark, 15 %of cross sectional area250.3 ft. MWL - Water Level, 10 %of cross sectional area250.3 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK250.3 ft. AMH - Downstream Manhole, Survey Begins - 14 0329A

Observation photos (17)

  • Water Mark, 15 %of cross sectional area

    0 ft. - Water Mark, 15 %of cross sectional area

  • Water Level, 10 %of cross sectional area

    0 ft. - Water Level, 10 %of cross sectional area

  • General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

    0 ft. - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

  • Downstream Manhole, Survey Begins - 14 0329A

    0 ft. - Downstream Manhole, Survey Begins - 14 0329A

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    25.7 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    45.2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    48.7 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    74.3 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    97 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    121.7 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    149.5 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Obstacles Pipe Material, 10 %of cross sectional area, from 06 to 08 o'clock

    150.2 ft. - Obstacles Pipe Material, 10 %of cross sectional area, from 06 to 08 o'clock

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    174.1 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    218.7 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    222.5 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Upstream Manhole, Survey Ends - 14 0330

    250.3 ft. - Upstream Manhole, Survey Ends - 14 0330

Observations (19)

DistanceCodeObservation
218.7TFC
45.2SSS
0MWM
149.5TFC
48.7TFC
174.1TFC
250.3AMH14 0330
0MWL
222.5TFC
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
25.7TFC
97TFC
247.7SSS
247.7SAP
74.3TFC
0AMH14 0329A
150.2OBM
3.1SAP
121.7TFC

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2014-12-10T02:41:17-08:00
documentation
PRO PIPE
is_lateral_inspection
false