Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 5, 2014, 10:17 AM
  • A 0244_A 0243_20141205_024302.mp4

Date
12/05/2014
W/O
475594
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00319
PipeID
P08019
Time
2:17 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1878
Sewer Name
A JOA-1A LONG BEACH WRP INTRCPTR, SECT 1, GRAVITY SWR
City
LONGBEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
21
Purpose
Routine Assessment
Project
WO_475594_TV03036_2014NOVEMBER
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Upstream MH
A 0244
Downstream MH
A 0243
Dir. of Survey
Downstream
Length Surveyed
669 ft.
Total Length
669 ft.
Structural Index
3
Structural Quick
513Z
Structural Rating
404
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
404
Pipe schematic from manhole A 0244 to A 0243
MH: A 0244MH: A 0243downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 02440 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start0 ft. MWM - Water Mark, 40 %of cross sectional area28.3 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES664.6 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish669 ft. AMH - Downstream Manhole, Survey Ends - A 0243

Observation photos (7)

  • Water Level, 30 %of cross sectional area

    0 ft. - Water Level, 30 %of cross sectional area

  • Upstream Manhole, Survey Begins - A 0244

    0 ft. - Upstream Manhole, Survey Begins - A 0244

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    0 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Water Mark, 40 %of cross sectional area

    0 ft. - Water Mark, 40 %of cross sectional area

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES

    28.3 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

    664.6 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

  • Downstream Manhole, Survey Ends - A 0243

    669 ft. - Downstream Manhole, Survey Ends - A 0243

Observations (7)

DistanceCodeObservation
28.3SRV
0MWL
0AMHA 0244
0SAV
0MWM
669AMHA 0243
664.6SAV

Properties (6)

custom_field_two
3
customer
LACSD
datetime
2014-12-05T02:17:13-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
19800819