Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 13, 2021, 07:09 AM
  • 02 1768_02 1767_8132021_004518.mp4

Date
08/13/2021
W/O
0890811
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00271
PipeID
P04115
Time
12:09 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1913
Sewer Name
02 INDIANA STREET TRUNK
City
LOS ANGLES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
11A
Purpose
Routine Assessment
Project
20210810MDM_INDINA_STREET_TRUNK
Material
NRCP
Shape
Circular
Height
7.53000020980835 in.
Upstream MH
02 1767
Downstream MH
02 1768
Dir. of Survey
Upstream
Length Surveyed
226.2 ft.
Total Length
226.2 ft.
Structural Index
3
Structural Quick
3321
Structural Rating
11
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
14
Pipe schematic from manhole 02 1767 to 02 1768
MH: 02 1767MH: 02 1768upstream0 ft. MSA - Survey Abandoned - INSPECTION COMPLETE REVERSE INSPECTION0.3 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish - FIBOROUS BLISTERING OUTER SURFACE0.3 ft. LFUC - Lining Failure Undercut Connection, at 01 o'clock, within 8 inches of joint: NO - SOIL VISIBLE AROUND CONN0.3 ft. LFUC - Lining Failure Undercut Connection, at 01 o'clock, within 8 inches of joint: NO - SOIL VISIBLE AROUND CONN0.3 ft. LFUC - Lining Failure Undercut Connection, at 01 o'clock, within 8 inches of joint: NO - SOIL VISIBLE INSDE CONN1.6 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO - SOIL18.1 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6" - Open59 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6" - Open122.6 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6" - Open140.8 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6" - Open202.1 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6", 6" - Open224.2 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - FIBOROUS BLISTERING OUTER LAYER226.2 ft. AMH - Downstream Manhole, Survey Begins - 12:35AM226.2 ft. MWL - Water Level, 5 %of cross sectional area226.2 ft. MWM - Water Mark, 20 %of cross sectional area

Observation photos (5)

  • Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - FIBOROUS BLISTERING OUTER LAYER

    2 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - FIBOROUS BLISTERING OUTER LAYER

  • Deposits Settled Other,  15 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO - SOIL

    224.6 ft. - Deposits Settled Other, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO - SOIL

  • Lining Failure Undercut Connection, at 01 o'clock, within 8 inches of joint: NO - SOIL VISIBLE AROUND CONN

    225.9 ft. - Lining Failure Undercut Connection, at 01 o'clock, within 8 inches of joint: NO - SOIL VISIBLE AROUND CONN

  • Lining Failure Undercut Connection, at 01 o'clock, within 8 inches of joint: NO - SOIL VISIBLE AROUND CONN

    225.9 ft. - Lining Failure Undercut Connection, at 01 o'clock, within 8 inches of joint: NO - SOIL VISIBLE AROUND CONN

  • Lining Failure Undercut Connection, at 01 o'clock, within 8 inches of joint: NO - SOIL VISIBLE INSDE CONN

    225.9 ft. - Lining Failure Undercut Connection, at 01 o'clock, within 8 inches of joint: NO - SOIL VISIBLE INSDE CONN

Observations (15)

DistanceCodeObservation
226.2MSAINSPECTION COMPLETE REVERSE INSPECTION
24.1TBOpen
103.6TBOpen
224.6DSZSOIL
208.1TBOpen
0AMH12:35AM
167.2TBOpen
2SSSFIBOROUS BLISTERING OUTER LAYER
225.9SSSFIBOROUS BLISTERING OUTER SURFACE
0MWL
225.9LFUCSOIL VISIBLE AROUND CONN
0MWM
225.9LFUCSOIL VISIBLE AROUND CONN
225.9LFUCSOIL VISIBLE INSDE CONN
85.4TBOpen

Properties (7)

custom_field_three
SOIL VISIBLE AROUIND CONN
custom_field_two
1
customer
LACSD
datetime
2021-08-13T00:09:42-07:00
documentation
MARTIN,OLIVER 111,BARR,RAMERIZ
is_lateral_inspection
false
lining
CIPP