Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 11, 2021, 08:17 AM
  • 02 1766_02 1765_8112021_024424.mp4

Date
08/11/2021
W/O
0890811
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00271
PipeID
P04113
Time
1:17 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1909
Sewer Name
02 INDIANA STREET TRUNK
City
LOS ANGLES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
11A
Purpose
Routine Assessment
Project
20210810MDM_INDINA_STREET_TRUNK
Material
NRCP
Shape
Circular
Height
7.53000020980835 in.
Upstream MH
02 1765
Downstream MH
02 1766
Dir. of Survey
Upstream
Length Surveyed
121.8 ft.
Total Length
121.9 ft.
Structural Index
2
Structural Quick
2300
Structural Rating
6
O&M Index
3
O&M Quick
3121
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
11
Pipe schematic from manhole 02 1765 to 02 1766
MH: 02 1765MH: 02 1766upstream0 ft. AMH - Upstream Manhole, Survey Ends(COMPLETED REVERSE INSPECTION) - 3:10AM0.9 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: NO, Finish - FIBOROUS BLISTERING OUTER SURFACE26.1 ft. MGO - General Observation - ZOOM 26'31.5 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - ROCKS ,SOIL,SLUDGE53.6 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: NO - FIBOROUS OUTER SURFACE102.1 ft. TBD - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: NO, 6" - Open 100% GREASE113.6 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: NO - FIBOROUS OUTER SURFACE119.9 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: NO, Start - FIBOROUS BLISTERING OUTER SURFACE121.9 ft. MWL - Water Level, 5 %of cross sectional area121.9 ft. MWM - Water Mark, 20 %of cross sectional area121.9 ft. AMH - Downstream Manhole, Survey Begins - 2:45AM

Observation photos (6)

  • Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: NO, Start - FIBOROUS BLISTERING OUTER SURFACE

    2 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: NO, Start - FIBOROUS BLISTERING OUTER SURFACE

  • Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: NO - FIBOROUS OUTER SURFACE

    8.3 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: NO - FIBOROUS OUTER SURFACE

  • Tap Break-In Defective, at 02 o'clock, -,  , within 8 inches of joint: NO, 6" - Open 100% GREASE

    19.8 ft. - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: NO, 6" - Open 100% GREASE

  • Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: NO - FIBOROUS OUTER SURFACE

    68.3 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: NO - FIBOROUS OUTER SURFACE

  • Deposits Settled Other,  10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES - ROCKS ,SOIL,SLUDGE

    90.4 ft. - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - ROCKS ,SOIL,SLUDGE

  • General Observation - ZOOM 26'

    95.8 ft. - General Observation - ZOOM 26'

Observations (11)

DistanceCodeObservation
0MWL
121.9AMH3:10AM
0MWM
68.3SSSFIBOROUS OUTER SURFACE
2SSSFIBOROUS BLISTERING OUTER SURFACE
90.4DSZROCKS ,SOIL,SLUDGE
19.8TBDOpen 100% GREASE
0AMH2:45AM
8.3SSSFIBOROUS OUTER SURFACE
95.8MGOZOOM 26'
121SSSFIBOROUS BLISTERING OUTER SURFACE

Properties (7)

custom_field_three
SPALLING FIBOROUS BLISTERING OUTER SURFACE
custom_field_two
4
customer
LACSD
datetime
2021-08-11T01:17:28-07:00
documentation
MARTIN,OLIVER 111,BARR,RAMERIZ
is_lateral_inspection
false
lining
CIPP