Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 14, 2021, 07:59 AM
  • B 1165_B 1164_07142021_010411.mp4

Date
07/14/2021
W/O
901874
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01125
PipeID
P13485
Time
12:59 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8677
Sewer Name
B JOINT OUTFALL B - UNIT 6H
City
SOUTH PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_901874_TV16072_JUL2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
B 1165
Downstream MH
B 1164
Dir. of Survey
Downstream
Length Surveyed
21.9 ft.
Total Length
21.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole B 1165 to B 1164
MH: B 1165MH: B 1164downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 11650 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area1.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start21.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish21.9 ft. AMH - Downstream Manhole, Survey Ends - B 1164

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    1.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (6)

DistanceCodeObservation
21.4DAGS
0AMHB 1165
0MWM
0MWL
21.9AMHB 1164
1.5DAGS

Properties (7)

additional_info
630138071321201
custom_field_three
NO STRUCTURAL DEFECTS
custom_field_two
4
customer
1
datetime
2021-07-14T00:59:33-07:00
documentation
PROPIPE
is_lateral_inspection
false