Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 14, 2021, 06:20 AM
  • B 1195_B 1194_07132021_232904.mp4

Date
07/13/2021
W/O
901874
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z01125
PipeID
P13515
Time
11:20 PM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8677
Sewer Name
B JOINT OUTFALL B - UNIT 6H
City
SOUTH PASADENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_901874_TV16072_JUL2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
B 1195
Downstream MH
B 1194
Dir. of Survey
Downstream
Length Surveyed
253.1 ft.
Total Length
253.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole B 1195 to B 1194
MH: B 1195MH: B 1194downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 11950 ft. MWM - Water Mark, 20 %of cross sectional area2.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start251.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish253.1 ft. AMH - Downstream Manhole, Survey Begins - B 1194

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (6)

DistanceCodeObservation
2.8DAGS
0MWL
253.1AMHB 1194
251.3DAGS
0AMHB 1195
0MWM

Properties (7)

additional_info
630138071321201
custom_field_three
NO STRUCTURAL DEFECTS
custom_field_two
3
customer
1
datetime
2021-07-13T23:20:42-07:00
documentation
PROPIPE
is_lateral_inspection
false