- Date
- 11/20/2014
- W/O
- 470382
- Weather
- Dry
- Operator/Surveyor
- C. DEHNER
- Sewer ID
- Z00891
- PipeID
- P19922
- Time
- 3:11 AM
- Certificate
- U-912-15963
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K1644
- Sewer Name
- 32 VALENCIA TRUNK
- City
- VALENCIA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 32
- Page No.
- 04
- Purpose
- Routine Assessment
- Project
- WO_470382_TV32028_2014OCTOBER
- Sewer Type
- GRAVITY
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 18 in.
- Upstream MH
- 32 0171
- Downstream MH
- 32 0170
- Dir. of Survey
- Downstream
- Length Surveyed
- 521.7 ft.
- Total Length
- 521.7 ft.
- Structural Index
- 2
- Structural Quick
- 2100
- Structural Rating
- 2
- O&M Index
- 2
- O&M Quick
- 412S
- O&M Rating
- 208
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 210
Pipe schematic from manhole 32 0171 to 32 0170 Observation photos (2)

6.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

76.9 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES