- Date
- 12/09/2014
- W/O
- 0471212
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00061
- PipeID
- P11614
- Time
- 2:35 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- D6428
- Sewer Name
- J JOINT OUTFALL J - UNIT 2B
- City
- LOMITA
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 33
- Purpose
- Routine Assessment
- Project
- 20141209MDM_JOINT_OUTFALL_J_UNIT_2B
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 8 in.
- Upstream MH
- J 0037
- Downstream MH
- J 0036
- Dir. of Survey
- Downstream
- Length Surveyed
- 16.2 ft.
- Total Length
- 16.2 ft.
- Structural Index
- 2
- Structural Quick
- 2111
- Structural Rating
- 3
- O&M Index
- 2
- O&M Quick
- 2100
- O&M Rating
- 2
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 5
Pipe schematic from manhole J 0037 to J 0036 Observation photos (4)

0 ft. - Water Level, 5 %of cross sectional area

7.8 ft. - Crack Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES

13.1 ft. - Fracture Circumferential, from 04 to 05 o'clock, within 8 inches of joint: YES - SLIGHT

14.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES