Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 20, 2014, 06:28 AM
  • 32 0212_32 0211_20141119_223558.mp4

Date
11/19/2014
W/O
470293
Weather
Dry
Operator/Surveyor
C. DEHNER
Sewer ID
Z00885
PipeID
P19967
Time
10:28 PM
Certificate
U-912-15963
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1643
Sewer Name
32 AVENUE SCOTT TRUNK
City
VALENCIA
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
04
Purpose
Routine Assessment
Project
WO_0470293_TV32003_2014OCTOBER
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
32 0212
Downstream MH
32 0211
Dir. of Survey
Downstream
Length Surveyed
79.6 ft.
Total Length
79.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
412B
O&M Rating
34
Overall Index
2
Overall Quick
Overall Rating
34
Pipe schematic from manhole 32 0212 to 32 0211
MH: 32 0212MH: 32 0211downstream0 ft. MGO - General Observation - Connec, @ Mh, 4 O' Clock. Capped0 ft. AMH - Upstream Manhole, Survey Begins - 32 02120 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. MWL - Water Level, 50 %of cross sectional area3.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start77.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish79.6 ft. AMH - Downstream Manhole, Survey Ends - 32 0211

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    3.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
0MGOConnec, @ Mh, 4 O' Clock. Capped
0AMH32 0212
0MWM
0MWL
3.3DAGS
77.6DAGS
79.6AMH32 0211

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2014-11-19T22:28:31-08:00
documentation
PROPIPE
is_lateral_inspection
false