Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 21, 2014, 08:33 AM
  • 32 0200_32 0085_20141121_005905.mp4

Date
11/21/2014
W/O
470293
Weather
Dry
Operator/Surveyor
C. DEHNER
Sewer ID
Z00885
PipeID
P19955
Time
12:33 AM
Certificate
U-912-15963
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1646
Sewer Name
32 AVENUE SCOTT TRUNK
City
VALENCIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
04
Purpose
Routine Assessment
Project
WO_0470293_TV32003_2014OCTOBER
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
32 0200
Downstream MH
32 0085
Dir. of Survey
Downstream
Length Surveyed
351.6 ft.
Total Length
351.6 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 32 0200 to 32 0085
MH: 32 0200MH: 32 0085downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 02003.7 ft. FC - Fracture Circumferential, from 09 to 07 o'clock, within 8 inches of joint: YES5.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES16.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN169.8 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE288 ft. TFA - Tap Factory Made Active, at 09 o'clock, 6", within 8 inches of joint: NO351.6 ft. AMH - Downstream Manhole, Survey Ends - 32 0085

Observation photos (5)

  • Fracture Circumferential, from 09 to 07 o'clock, within 8 inches of joint: YES

    3.7 ft. - Fracture Circumferential, from 09 to 07 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES

    5.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN

    16.3 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE

    169.8 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE

  • Tap Factory Made Active, at 09 o'clock, 6", within 8 inches of joint: NO

    288 ft. - Tap Factory Made Active, at 09 o'clock, 6", within 8 inches of joint: NO

Observations (9)

DistanceCodeObservation
169.8TBACTIVE
16.3TBOPEN
3.7FC
0MWL
0MWM
0AMH32 0200
351.6AMH32 0085
5.2DAGS
288TFA

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2014-11-21T00:33:27-08:00
documentation
PROPIPE
is_lateral_inspection
false