Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 19, 2014, 08:44 AM
  • B 0739_B 0738_20141119_005730.mp4

Date
11/19/2014
W/O
470341
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00111
PipeID
P09206
Time
12:44 AM
Certificate
03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1669
Sewer Name
B JOINT OUTFALL B - UNIT 8H
City
MONROVIA, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
06
Purpose
Routine Assessment
Project
WO_0470341_TV15139_2014OCTOBER
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
B 0738
Downstream MH
B 0739
Dir. of Survey
Upstream
Length Surveyed
152.9 ft.
Total Length
152.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole B 0738 to B 0739
MH: B 0738MH: B 0739upstream0 ft. MGO - General Observation - CONNECTION AT MANHOLE ACTIVE 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - B 0739 (00:55)1.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish50 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4" - OPEN60 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"150.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start152.9 ft. MGO - General Observation - CONNECTION AT MANHOLE ACTIVE 9 O'CLOCK152.9 ft. MWM - Water Mark, 20 %of cross sectional area152.9 ft. AMH - Downstream Manhole, Survey Begins - B 0738 (00:44)152.9 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (9)

  • General Observation - CONNECTION AT MANHOLE ACTIVE 9 O'CLOCK

    0 ft. - General Observation - CONNECTION AT MANHOLE ACTIVE 9 O'CLOCK

  • Water Mark, 20 %of cross sectional area

    0 ft. - Water Mark, 20 %of cross sectional area

  • Water Level, 10 %of cross sectional area

    0 ft. - Water Level, 10 %of cross sectional area

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"

    92.9 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4" - OPEN

    102.9 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4" - OPEN

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO, Finish

    151.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish

  • General Observation - CONNECTION AT MANHOLE ACTIVE 3 O'CLOCK

    152.9 ft. - General Observation - CONNECTION AT MANHOLE ACTIVE 3 O'CLOCK

  • Upstream Manhole, Survey Ends - B 0739 (00:55)

    152.9 ft. - Upstream Manhole, Survey Ends - B 0739 (00:55)

Observations (10)

DistanceCodeObservation
92.9TFC
151.2DAGS
102.9TBOPEN
0MGOCONNECTION AT MANHOLE ACTIVE 9 O'CLOCK
152.9MGOCONNECTION AT MANHOLE ACTIVE 3 O'CLOCK
0MWM
152.9AMHB 0739 (00:55)
0AMHB 0738 (00:44)
0MWL
2DAGS

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2014-11-19T00:44:18-08:00
documentation
PRO-PIPE
is_lateral_inspection
false