Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 19, 2014, 08:59 AM
  • 0_B 0739_20141119_012341.mp4

Date
11/19/2014
W/O
470341
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00111
PipeID
P21414
Time
12:59 AM
Certificate
03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1669
Sewer Name
B JOINT OUTFALL B - UNIT 8H
City
MONROVIA, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
06
Purpose
Routine Assessment
Project
WO_0470341_TV15139_2014OCTOBER
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
B 0739
Downstream MH
0
Dir. of Survey
Upstream
Length Surveyed
334 ft.
Total Length
334 ft.
Structural Index
4
Structural Quick
4200
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole B 0739 to 0
MH: B 0739MH: 0upstream0 ft. AMH - Upstream Manhole, Survey Ends - 0 (01:21)24.7 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 4"47 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4" - W/ OFFSET149 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish152.4 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start247.3 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"262.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"334 ft. MWL - Water Level, 15 %of cross sectional area334 ft. MWM - Water Mark, 15 %of cross sectional area334 ft. MGO - General Observation - CONNECTION AT MANHOLE ACTIVE 3 O'CLOCK334 ft. AMH - Downstream Manhole, Survey Begins - B 0739 (01:01)

Observation photos (5)

  • General Observation - CONNECTION AT MANHOLE ACTIVE 3 O'CLOCK

    0 ft. - General Observation - CONNECTION AT MANHOLE ACTIVE 3 O'CLOCK

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    71.7 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    86.7 ft. - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    181.6 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 4"

    309.3 ft. - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 4"

Observations (11)

DistanceCodeObservation
334AMH0 (01:21)
181.6FM
287TFAW/ OFFSET
0MWL
309.3TBA
71.7TFC
0MWM
0MGOCONNECTION AT MANHOLE ACTIVE 3 O'CLOCK
185FM
86.7TBA
0AMHB 0739 (01:01)

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2014-11-19T00:59:44-08:00
documentation
PRO-PIPE
is_lateral_inspection
false