Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 14, 2014, 06:02 AM
  • 15 0031_15 0030_20141113_223139.mp4

Date
11/13/2014
W/O
470269
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00622
PipeID
P11921
Time
10:02 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1855
Sewer Name
15 PUENTE TRUNK
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
34
Purpose
Routine Assessment
Project
WO_0470269_TV15026_2014OCTOBER_1
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
15 0031
Downstream MH
15 0030
Dir. of Survey
Downstream
Length Surveyed
389.4 ft.
Total Length
389.4 ft.
Structural Index
3
Structural Quick
3221
Structural Rating
8
O&M Index
2
O&M Quick
412A
O&M Rating
24
Overall Index
2
Overall Quick
Overall Rating
32
Pipe schematic from manhole 15 0031 to 15 0030
MH: 15 0031MH: 15 0030downstream0 ft. DSF - Deposits Settled Fine, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 00310 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MANHOLE 4 O'CLOCK, ACTIVE23.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"28.8 ft. FC - Fracture Circumferential, from 01 to 05 o'clock, within 8 inches of joint: YES50.8 ft. DSF - Deposits Settled Fine, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish50.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"70.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"93.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"121.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"140.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"158 ft. CM - Crack Multiple, from 07 to 09 o'clock, within 8 inches of joint: YES164.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"191.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"204.9 ft. CM - Crack Multiple, from 10 to 11 o'clock, within 8 inches of joint: YES214.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"241.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"268.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"291.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"319.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"330.3 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE343.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"371.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"389.4 ft. AMH - Downstream Manhole, Survey Ends - 15 0030

Observation photos (26)

  • Deposits Settled Fine,  10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Settled Fine, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Water Mark, 60 %of cross sectional area

    0 ft. - Water Mark, 60 %of cross sectional area

  • Upstream Manhole, Survey Begins - 15 0031

    0 ft. - Upstream Manhole, Survey Begins - 15 0031

  • Water Level, 50 %of cross sectional area

    0 ft. - Water Level, 50 %of cross sectional area

  • General Observation - CONNECTION AT MANHOLE 4 O'CLOCK, ACTIVE

    0 ft. - General Observation - CONNECTION AT MANHOLE 4 O'CLOCK, ACTIVE

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    23.4 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Fracture Circumferential, from 01 to 05 o'clock, within 8 inches of joint: YES

    28.8 ft. - Fracture Circumferential, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Deposits Settled Fine,  10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Finish

    50.8 ft. - Deposits Settled Fine, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    50.8 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    70.5 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    93.7 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    121.9 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    140.1 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 07 to 09 o'clock, within 8 inches of joint: YES

    158 ft. - Crack Multiple, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    164.1 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    191.4 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 10 to 11 o'clock, within 8 inches of joint: YES

    204.9 ft. - Crack Multiple, from 10 to 11 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    214.6 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    241.2 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    268.1 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    291.7 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    319.6 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE

    330.3 ft. - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    343.2 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    371.1 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Downstream Manhole, Survey Ends - 15 0030

    389.4 ft. - Downstream Manhole, Survey Ends - 15 0030

Observations (26)

DistanceCodeObservation
371.1TFC
204.9CM
121.9TFC
0DSF
268.1TFC
50.8DSF
0MWM
241.2TFC
191.4TFC
389.4AMH15 0030
0AMH15 0031
164.1TFC
93.7TFC
70.5TFC
319.6TFC
0MWL
140.1TFC
158CM
23.4TFC
28.8FC
0MGOCONNECTION AT MANHOLE 4 O'CLOCK, ACTIVE
50.8TFC
330.3TBACTIVE
214.6TFC
343.2TFC
291.7TFC

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2014-11-13T22:02:47-08:00
documentation
PROPIPE
is_lateral_inspection
false