Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 14, 2014, 08:05 AM
  • 15 0027_15 0026_20141114_002718.mp4

Date
11/14/2014
W/O
470269
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00622
PipeID
P11917
Time
12:05 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1855
Sewer Name
15 PUENTE TRUNK
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
34
Purpose
Routine Assessment
Project
WO_0470269_TV15026_2014OCTOBER_1
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
15 0027
Downstream MH
15 0026
Dir. of Survey
Downstream
Length Surveyed
446.7 ft.
Total Length
446.7 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2B00
O&M Rating
30
Overall Index
2
Overall Quick
Overall Rating
36
Pipe schematic from manhole 15 0027 to 15 0026
MH: 15 0027MH: 15 0026downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 00270 ft. MGO - General Observation - CONNECTION AT MANHOLE 3 O'CLOCK,A CTIVE0 ft. MWL - Water Level, 10 %of cross sectional area31.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"77 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start92.7 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"112.9 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"137.9 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"163.3 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"181.8 ft. CM - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES188.6 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"213.6 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"231.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES239 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"264.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"289.9 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"315.2 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"340.4 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"365.4 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN395.7 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"416 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"436.1 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"442.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish446.7 ft. AMH - Downstream Manhole, Survey Ends - 15 0026

Observation photos (25)

  • Water Mark, 20 %of cross sectional area

    0 ft. - Water Mark, 20 %of cross sectional area

  • Upstream Manhole, Survey Begins - 15 0027

    0 ft. - Upstream Manhole, Survey Begins - 15 0027

  • General Observation - CONNECTION AT MANHOLE 3 O'CLOCK,A CTIVE

    0 ft. - General Observation - CONNECTION AT MANHOLE 3 O'CLOCK,A CTIVE

  • Water Level, 10 %of cross sectional area

    0 ft. - Water Level, 10 %of cross sectional area

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    31.9 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    77 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    92.7 ft. - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    112.9 ft. - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    137.9 ft. - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    163.3 ft. - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

    181.8 ft. - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    188.6 ft. - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    213.6 ft. - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    231.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    239 ft. - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    264.3 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    289.9 ft. - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    315.2 ft. - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    340.4 ft. - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

    365.4 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

  • Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    395.7 ft. - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    416 ft. - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    436.1 ft. - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Finish

    442.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish

  • Downstream Manhole, Survey Ends - 15 0026

    446.7 ft. - Downstream Manhole, Survey Ends - 15 0026

Observations (25)

DistanceCodeObservation
0MWM
112.9TBC
289.9TBC
436.1TBC
264.3TFC
188.6TBC
163.3TBC
92.7TBC
340.4TBC
231.6CM
442.7DAGS
446.7AMH15 0026
0AMH15 0027
181.8CM
416TBC
77DAGS
365.4TBOPEN
315.2TBC
213.6TBC
0MGOCONNECTION AT MANHOLE 3 O'CLOCK,A CTIVE
137.9TBC
239TBC
0MWL
31.9TB
395.7TBC

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2014-11-14T00:05:13-08:00
documentation
PROPIPE
is_lateral_inspection
false